IFM ioControl CR2050 Manuel D'utilisation page 115

Table des Matières

Publicité

Manufacturer-specific objekts (index 0x2000���0x6FFF):
Index
S-idx
Designation
0x2000
0x00
IO configu-
ration
Largest
sub-index
supported
0x01
Configuration
IN00
0x02
Configuration
IN01
0x03
Configuration
IN02
0x04
Configuration
IN03
Data type
Default
ro
USINT
16
rw
USINT
10
rw
USINT
10
rw
USINT
10
rw
USINT
10
Details (CR2052)
Configuration inputs/outputs
largest supported Sub-index = 32
0 = 0x00
off Input IN00
3 = 0x03
0���10 000 mV
6 = 0x06
ratiometric 0���1000 ‰
7 = 0x07
0���20 000 µA
9 = 0x09
0���32 000 mV
10 = 0x0A
binary plus switched
11 = 0x0B
binary plus switched
with diagnosis
12 = 0x0C
binary minus switched
14 = 0x0E
frequency
0...30 000 Hz
20 = 0x14
period duration as
ratio 0...1 000 ‰
0 = 0x00
off Input IN01
3 = 0x03
0���10 000 mV
6 = 0x06
ratiometric 0���1000 ‰
7 = 0x07
0���20 000 µA
9 = 0x09
0���32 000 mV
10 = 0x0A
binary plus switched
11 = 0x0B
binary plus switched
with diagnosis
12 = 0x0C
binary minus switched
14 = 0x0E
frequency
0...30 000 Hz
20 = 0x14
period duration as
ratio 0...1 000 ‰
0 = 0x00
off Input IN02
10 = 0x0A
binary plus switched
11 = 0x0B
binary plus switched
with diagnosis
18 = 0x12
16...30 000 Ohm
0 = 0x00
off Input IN03
10 = 0x0A
binary plus switched
11 = 0x0B
binary plus switched
with diagnosis
18 = 0x12
16...30 000 Ohm
ioControl
UK
115

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Iocontrol cr2051Iocontrol cr2052

Table des Matières