TEMP V4 IP68 LoRaWAN 863-870 - Guide utilisateur / User guide version V3.1.1
2.4.1 Periodical transmission with or without historisation
The product enables to measure and send the data from the probe following the diagram bellow.
This periodical transmission can be done with or without historisation of the data.
The product enables to activate or deactivate a probe. The 0x57 frame will be different depending if 1 or 2 probes are activated.
FR
Parameters associated to this mode are:
• Sampling period (register S321), historisation frequency (register S320) and transmission frequency (register S301)
• Activation of the probes (register S324).
EN
Stand-by mode
Sampling peri-
od reached?
Temperature
measure and saving
Temperature
measure and saving
Historisation
Transmission
Sending 0x57
No
Yes
probe 1
probe 2
No
frequency
reached?
Yes
No
frequency
reached?
Yes
Example without historisation:
Register Encoding
Value
S321
Decimal
1800
S320
Decimal
1
S301
Decimal
1
S324
Decimal
3
In this example:
• 1 sample (reading) every hour (1800 x 2 seconds = 60 minutes)
• 1 historisation at each sample and the frame is sent immediately (so every
hour)
• The 2 probes are activated so the product will read the temperature on the 2
probes every hour.
Example with historisation:
Register Encoding
Value
S321
Decimal
1800
S320
Decimal
1
S301
Decimal
12
S324
Decimal
3
In this example:
• A sample (reading) every hour (1800x2secondes = 60 minutes)
• An historisation done at each sampling (so every hours)
• A transmission is done every 12 historisations (so every 12 hours, so 2 times
a day)
• The 2 probes are activated so the product will read the temperature on the 2
probes every hour.
Result
1 sample every hour
(1800 x 2 seconds = 60 minutes)
1 historisation for each sample
1 transmission for each historisation
The 2 probes are activated
Result
1 sample every hour
(1800 x 2 seconds = 60 minutes)
1 historisation for each sample
1 transmission every 12 historisations
The 2 probes are activated
50 of 61