2.2.2

Periodic transmission with history

The product allows the accumulation of several successive meter values before the periodic transmis-
sion of the set of values according to the following scheme:
No
No
The settings associated with this mode of operation are:
Enabling and Configuring inputs (register 320)
History configuration (register S321)
Anti-bounce timer period (registers S322)
A complete list of the registers can be found in paragraph 3.4.
Eg:
Register
Value encoding
S320
Hexadecimal
S321
Hexadecimal
S322
Hexadecimal
Product in
standby
Historical
period
reached
?
Yes
Number
of record-
ed values
reached ?
Yes
Send frame 0x48
Detected and
validated
pulse
?
Yes
Counting
of the impulse
Value
Result
0x39
Channel A :
Activated
Meter other than gas
Tamper input activated
Channel B :
Activated
Gas meter
Tamper input disabled
0x02
Channels A and B : historical mode with back-
up of the counters every hour and transmis-
sion every 24h so 24 values per counter
0x57
Anti-bounce :
Channel A = 500ms
Channel B = 100ms