Frame Of Information On The Network Configuration; Keep Alive Frame - ADEUNIS ARF8230AA Guide Utilisateur

Masquer les pouces Voir aussi pour ARF8230AA:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN 863-870 Pulse - Guide utilisateur / User guide version V2.0.0
4.1.3

Frame of information on the network configuration

Following reception of a downlink frame with the code 0x02 or on switching to the operating mode
(from the Park or Command Mode), the next frame (0x20) representing the network configuration of
the product is transmitted:
0
Code
Status
0x20
Cf Status
0x20
0xA3
Its size is of 4 bytes.
Description of the frame:
Byte 2 : register S220 : Activation of Adaptative Data Rate
Byte 3 : register S221 : connexion mode
In the example in grey this gives:
Byte 2=0x05 : Adaptative Data Rate is activated
Byte 3=0x01 : connexion mode is OTAA
4.1.4

Keep Alive frame

This frame (0x30) is transmitted 24 hours after the startup of the application or after the transmission
of the previous Keep Alive frame. In TEST mode, this frame is transmitted every 5 minutes.
0
1
Code
Status
0x30
Cf Status
0x30
0xA3
Its size is of 11 bytes.
Description of the frame:
Byte 2 : Alarms state (bit to 1 if the alarm is activated else 0) :
Bit 0 – Exceeding flow on channel A
Bit 1 – Exceeding flow on channel B
Bit 2 – Tamper detected on channel A
Bit 3 – Tamper detected on channel B
Bit 4 – Leak detected on channel A
Bit 5 – Leak detected on channel B
Bit 6/7 – Reserved
Bytes 3 to 4 : maximum measured flow on channel A within the last 24 hours.
Bytes 5 to 6 : maximum measured flow on channel B within the last 24 hours.
Bytes 7 to 8 : minimum measured flow on channel A within the last 24 hours.
Bytes 9 to 10 : minimum measured flow on channel B within the last 24 hours.
In the example in grey this gives:
Byte 2 : Alarms = 0x19 so as (00011001) binary which gives:
Bit 0 = 1 – Exceeding flow on channel A
Bit 1 = 0 – No exceeding flow on channel B
Bit 2 = 0 – No tamper detected on channel A
Bit 3 = 1 – Tamper detected on channel B
Bit 4 = 1 – Leak detected on channel A
Bit 5 = 0 – No leak detected on channel B
Bit 6/7 – Reserved
1
2
PAYLOAD
S220
0x05
2
Max flow -
Alarms
0x19
3
S221
0x01
3 - 4
5 - 6
PAYLOAD
Max flow -
channel A
channel B
0x310A
0x12C4
7 - 8
9 - 10
Min flow -
Min flow -
channel A
channel B
0x0010
0x0000
Page
87
FR
EN
of 108

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Arf8230fa

Table des Matières