2.4.4 Transmission on threshold overpassed with alarm repetition

The product enables the detection of a threshold overpassed (high and low) for each probe and to repeat this alert depending on a determined
Stand-by mode
FR
Sampling peri-
od reached?
EN
Temperature
on probe 1 and/or 2
overpassed?
Sending 0x58*
Alarm repeti-
tion activated?
0x58 frame repetition
every S321 x S322
Come back to
Sending 0x58*
No
Yes
sampling
No
Threshold
Yes
No
Yes
No
normal?
Yes
*The "alarm status" byte gives the information if the alert is activated or not and so allows
to dissociate a 0x58 frame sent to alert that the threshold is overpassed from a 0x58 frame
sent to inform about come back to normal.
period (register S321 x S322).
Settings associated to this operating mode are:
• Sampling period (register 321),
• Alarm repetition (register 322),
• Activation of the probes (register 324).
• Alarm configuration on probe 1 (register 330) and probe 2 (register 340).
• High threshold on the probe 1 (register 331) and probe 2 (register 341).
• Hysteresis for high threshold on probe 1 (register 332) and probe 2 (register 342).
• Low threshold on the probe 1 (register 333) and probe 2 (register 343).
• Hysteresis for low threshold on probe 1 (register 334) and probe 2 (register 344).
Example:
Registers
Encoding
Value
S301
Decimal
0
S324
Decimal
1
S330
Decimal
3
S331
Decimal
700
S332
Decimal
50
S333
Decimal
100
S334
Decimal
20
S321
Decimal
300
S322
Decimal
2
In this example:
• The product measure temperature only on probe 1
• On probe 1, there is a high threshold at 70°C with a come back to normal at 65°C
and a low threshold at10°C with a come back to normal at 12°C
• A sampling (reading) every 10 minutes (300 x 2 seconds = 10 minutes)
• As long as the alarm is active (threshold always overpassed), this alarm will be
repeated every 2 samples (so every 20 minutes).
Result
Alarm mode
Only probe 1 is activated
High and low threshold activated on probe 1
High threshold is 70°C
Hysteresis for high threshold is 5°C, the
come back to normal is at 65°C
Low threshold is 10°C
Hysteresis for low threshold is 2°C, the come
back to normal is at 12°C
A sampling is done every 10 minutes (300 x
2 seconds = 10 minutes)
Alarm will be sent every 2 sampling if
always activated
54 of 61