164 Test contacts H
= contact
closed
= contact open
165 Flow temperature
setpoint
en
166 Resulting heating
curve
167 Outside temp. for
frost protection for
the plant
168 Flow temp. setpoint
for frost protection
for the plant
169 Device number
170 Segment number
171 Flow alarm
Building Technologies
Display function
Display function
Display function
2.0 °C
(--.- / 0...25.0)
...................
15 °C
(0...140)
...................
0
(0...16)
.........................
0
(0...14)
.........................
--:-- h
(--:-- / 1:00...10:00)
......................
74 319 0619 0 a
H1 = overriding the operating
mode
H2 = manually generated heat
demand
Current setpoint according to
the composite outside tempera-
ture, heating curve, setting knob
position and setting on operat-
ing line 72
Setpoint incl. setting knob posi-
tion and setting on operating
line 72
Left: Flow setpoint at 15 °C
outside temperature
Right: Flow setpoint at –5 °C
outside temperature
Setting --.- = no frost protection
for the plant
°C
°C
Data bus address (LPB)
0 = device with no bus
Data bus address (LPB)
Period of time during which the
flow/boiler temperature may
h
stay outside the limit values.
Plant types 1–x, 2–x, and 3–x:
sensor B1
Plant types 4–x and 5–x:
sensor B2
--.-- = function deactivated
17.04.2008
60/288