Settings on the "Heating engineer" level
Press
and
simultaneously for 3 seconds to activate the "Heating engineer" level for se-
lecting the plant type and the plant-related variables.
Selecting the plant type on operating line 51:
The required plant type must be selected on operating line 51 using buttons
activates all functions required for the respective type of plant and shows the associated operat-
ing lines.
A plant type is comprised of a space heating circuit (5 different types) and a d.h.w. circuit (4
different types). The 2 types of circuits can be combined in 21 different ways. The following plant
diagrams show all possible combinations.
The controller's operating line 51 only accepts combinations that are possible.
Example of a setting:
51
Plant type
Plant types
A6
Room unit
B1
Flow temperature sensor
B2
Boiler temperature sensor
B3
Flow temperature sensor for d.h.w.
B31 D.h.w. storage tank temperature sensor / thermostat 1
B32 D.h.w. storage tank temperature sensor / thermostat 2
B5
Room temperature sensor
B6
Collector sensor
B7
Return temperature sensor
B9
Outside sensor
E1
Heat source (boiler)
E2
Consumer (space)
LPB Data bus
Building Technologies
1 = Space heating type 1
2 = d.h.w. circuit type 2
2−1
(1−0 ... 5−4)
.........................
K6
Electric immersion heater
M1 Circulating pump / bypass pump
M2 Heating circuit pump
M3 Charging pump
M4 Boiler pump or circulating pump
M5 Collector pump
N1
Controller RVL482
U1
Solar sensor
U2
Wind sensor
Y1
Heating circuit mixing valve
Y7
D.h.w. mixing valve or mixing valve for minimum
limitation of the boiler return temperature
74 319 0619 0 a