142 Outside tempera-
ture switch
Switch-off value for
occupancy time
143 Outside tempera-
ture switch
Switch-off value for
non-occupancy time
144 Outside tempera-
ture switch
Switching differen-
tial
145 Selection time
switch
146 Outside tempera-
ture switch
Switch-off value for
occupancy time
Block "Legionella function"
147 Periodicity of le-
gionella function
148 Time for charging
149 Dwelling time at
legionella setpoint
150 Circulating pump
operation during
legionella function
Building Technologies
0
(0 / 1)
.........................
5.0 °C
(−35.0...+35.0)
...................
−5.0 °C
(−35.0...+35.0)
...................
3 °C
(1...20)
...................
3
(1...3)
.........................
1
(0...7)
.........................
05:00
(00:00...24:00)
.........................
30 min
(0...360)
min
................
1
(0 / 1)
.........................
74 319 0619 0 a
0 = relay DEENERGIZED
1 = relay ENERGIZED
Function can be provided only
when operating line 141 = 7
Function can be provided only
°C
when operating line 141 = 1
Function can be provided only
°C
when operating line 141 = 1
Function can be provided only
°C
when operating line 141 = 1
1 = heating program
2 = switching program 2
3 = switching program 3
0 = daily
1...7 = weekly, whereby
1 = always on Monday
2 = always on Tuesday; etc.
For setpoint of legionalla func-
tion, refer to line 130
0 = no impact on the circulating
pump
1 = with impact on the circulat-
ing pump
17.04.2008
en
57/288