126 D.h.w. temperature
sensor / d.h.w. ther-
mostat
127 D.h.w. charging
temperature boost
128 D.h.w. switching
differential
129 Maximum d.h.w.
charging time
130 Setpoint of le-
gionella function
131 Forced charging
Block "3-position actuator d.h.w."
132 Flow temperature
boost mixing valve /
heat exchanger
Building Technologies
0
(0...5)
.........................
10 °C
(0...50)
°C
...................
8 °C
(1...20)
°C
...................
60 min
(--- / 5...250)
min
................
--- °C
(--- / 20...100)
°C
...................
0
(0 / 1)
.........................
10 °C
(0...50)
°C
...................
74 319 0619 0 a
3 = alternating with space heat-
ing / electric; changeover ac-
cording to all controllers in the
interconnected system
If operating line 54 = 3, this
operating line cannot be
changed. In that case, charging
always takes place via space
heating
0 = 1 sensor
1 = 2 sensors
2 = 1 thermostat
3 = 2 thermostats
4 = 1 sensor, with solar d.h.w.
heating
5 = 2 sensors, with solar d.h.w.
heating
Plant types x–4 without solar
charging: setting = 0
Setting --- = function deacti-
vated
Setting --- = function deacti-
vated
0 = none
1 = daily on first release
17.04.2008
en
55/288