Block "Release, priority and flow temperature setpoint of d.h.w. heating"
123 Release of d.h.w.
heating
en
124 D.h.w. priority, flow
temperature set-
point
Block "D.h.w. storage tank"
125 D.h.w. heating
Building Technologies
2
(0...2)
.........................
0
(0...4)
.........................
0
(0...3)
.........................
74 319 0619 0 a
0 = released 24 hours a day
1 = released according to the
heating program(s), de-
pending on the setting
made on operating line 121;
start of release is shifted
forward by one hour
2 = released according to
switching program 2
D.h.w.
Flow setpoint
priority
according to
0 = absolute
D.h.w.
priority
1 = shifting
D.h.w.
priority
2 = shifting
Maximum
priority
selection
3 = none
D.h.w.
(parallel)
4 = none
Maximum
(parallel)
selection
0 = parallel with space heating
1 = alternating with space heat-
ing / electric; changeover ac-
cording to own controller
2 = alternating with space heat-
ing / electric; changeover ac-
cording to all controllers in
the interconnected system
that have the same segment
number
17.04.2008
54/288