Ecolab MULTRONIC Manuel Technique page 16

Masquer les pouces Voir aussi pour MULTRONIC:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Timer Modul
If precirculation is interrupted because the release is discontinued, the pre-circulation time
is reset. The time starts to elapse again once the release has been granted again.
precirculation starts specifies the number of times precirculation can be restarted. If the
number of starts is exceeded, the biocide metering is interrupted and the alarm message is
shown.
Value range: 1 to 99. Off switches off monitoring.
The maximum interruption time defines the length of time for which biocide metering can be
interrupted if the release is discontinued. The interruption time affects pre-circulation,
advanced desalting, and metering. The impact process is not monitored. If the maximum
interruption time is exceeded, the biocide metering is interrupted and the alarm message is
shown.
Value range: 0 to 99. Off switches off monitoring.
417101824_Anhang13_Timermodul.doc
- 16 -
Rev.: 4-07/10

Publicité

Table des Matières
loading

Table des Matières