Connection Of The Sauna Heater To The Mains; Electric Heating Toggle - Helo HAVANNA D -WT Manuel Du Produit

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 63
Installation and User Manual Havanna D Helo-WT
Power
Saunaroom
Volume
min.
max.
kW
4,5
3
6
6,0
5
9
8,0
8
12
9,0
9
13
Table 1 Safety clearances

2.11. Connection of the sauna heater to the mains

The sauna heater must be connected to the mains by a qualified electrician and in compliance with current regulations. Sauna
heater is connected with a semi-permanent connection. Use H07RN-F (60245 IEC 66) cables or a corresponding type. Other
output cables (signal lamp, electric heating toggle) must also adhere to these recommendations. Do not use PVC insulated
cable as a connection cable for the sauna heater.
A multipolar (e.g. 7-pole) cable is allowed, if the voltage is the same. In the absence of a separate control current fuse, the
diameter of all cables must be the same, i.e. in accordance with the front fuse. For example, in an 8 kW sauna heater the
diameter of separate cables to the signal lamp and the mains control unit has to be at least 2.5 mm².
The connecting box on the sauna wall should be located within the minimum safety clearance specified for the sauna heater.
The maximum height for the connection box is 500 mm from the floor (Image 6 Location for the connection box, page 10). If the
connection box is located at 500 mm distance from the heater, the maximum height is 1000 mm from the floor.
NOTE: Controlling the lights in the sauna with the circuit board is only possible with resistive loads (incandescent light bulbs).
The circuit board relay cannot withstand capacitive loads (switched-mode power supply units). If the lighting fixtures in the
sauna have transformers, for example LED or halogen lamps, the stove circuit board's relay control must be fitted with a
separate relay or contactor for controlling the lights.
Sauna heater insulation resistance: The sauna heater heating elements may absorb moisture from air, e.g. during storage. This
may cause bleeder currents. The moisture will be gone after a few heating sessions. Do not connect the heater power supply
through a ground fault interrupter.
Adhere to the effective electrical safety regulation when installing the sauna heater.
Power
Sauna heater's
connection cable
H07RN –F/
60245 IEC 66
mm²
kW
400V 3N~
4,5
5 x 1,5
6,0
5 x 1,5
8,0
5 x 2,5
9,0
5 x 2,5
Table 2 Connection cable and fuses

2.12. Electric heating toggle

Electric heating toggle applies to homes with an electric heating system.
Sauna heater has connections (marked N-55) for controlling the electric heating toggle. Connectors N-55 and the heating
elements are simultaneously live (230V). The sauna heater thermostat also controls the heating toggle. In other words,
home heating turns on once the sauna thermostat cuts power off the sauna heater.
Minimum distance to
Height
Side
In front
wall
of
A
D
mm
min. mm
mm
1900
40
80
1900
45
100
1900
75
130
1900
80
150
Fuse
Sauna heater's
connection cable
H07RN –F/
60245 IEC 66
A
mm²
230V 3~
3 x 10
4 x 2,5
3 x 10
4 x 2,5
3 x 16
4 x 6
3 x 16
4 x 10
Ceiling
Floor
K
B
mm
mm
mm
mm
1100
120
135
245
1100
120
140
245
1100
150
170
275
1100
150
175
275
Fuse
Sauna heater's
connection cable
H07RN –F/
60245 IEC 66
A
230V 1 N~ / 2~
3 x 16
3 x 16
3 x 25
3 x 35
Stone
min.
max.
Circa
Circa
J
kg
kg
20
28
20
35
20
35
20
35
Fuse
mm²
A
3 x 4
1 x 20
3 x 10
1 x 35
3 x 10
1 x 35
----------
--------
9

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

1714–450–041714–600–041714–800–041714–900–04

Table des Matières