Wiring the device modules
Safety modules
X82.3
X82.4
Cable cross-sections and tightening torques
Type
Wire end ferrule,
insulated
Rigid
Stripping length or contact length: 9 mm
116
Labelling
Description
GCL
GND clock output
GI2
GND IN I2A/I2B
I2B
Sensor input 2, channel B (only for passive sensors)
I2A
Sensor input 2, channel A (only for passive sensors)
GCL
GND clock output
GI1
GND I1A/I1B
I1B
Sensor input 1, channel B (only for passive sensors)
I1A
Sensor input 1, channel A (only for passive sensors)
n. c.
This terminal is not assigned.
Labelling
Description
GCL
GND clock output
GI4
GND I4A/I4B
I4B
Sensor input 4, channel B (only for active sensors)
I4A
Sensor input 4, channel A (only for active sensors)
n. c.
n. c.
This part of the terminal strip is not assigned.
n. c.
Sensor input 3 is not available.
n. c.
n. c.
2
[mm
]
0.25 ... 0.5
0.14 ... 1.5
[Nm]
AWG
24 ... 20
Spring terminal
26 ... 16
[lb-in]
Spring terminal