Mitsubishi Electric PUHZ-SWHA Série Manuel D'installation page 9

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
7. Electrical work
7.2. Field electrical wiring
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity Main switch (Breaker)
Outdoor unit power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
*2. Max. 45 m
If 2.5 mm
2
used, Max. 50 m
2
If 2.5 mm
used and S3 separated, Max. 80 m
*3. The 10 m wire is attached in the remote controller accessory.
*4. The fi gures are NOT always against the ground.
S3 terminal has 24 VDC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national codes.
2. Power supply cables and the cables between Interface unit/Flow temp. controller and outdoor unit shall not be lighter than polychloroprene sheathed
fl exible cables. (Design 60245 IEC 57)
3. Be sure to connect the cables between Interface unit/Flow temp. controller and outdoor unit directly to the units (no intermediate connections are al-
lowed).
Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may cause insuffi cient insulation
to ground or a poor electrical contact.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)
4. Install an earth longer than other cables.
5. Do not construct a system with a power supply that is turned ON and OFF frequently.
Warning:
· In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when
the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fi re or communication failure.
SW50V
~/N (single),
50 Hz, 230 V
*1
16 A
3 × Min. 1.5
*2
3 × 1.5 (Polar)
*2
1 × Min. 1.5
*3
2 × 0.3 (Non-polar)
*4
230 VAC
*4
230 VAC
*4
24 VDC
*4
12 VDC
Power
supply
Isolator
S1
S2
Outdoor Unit
S3
SW75V
SW100V
~/N (single),
~/N (single),
50 Hz, 230 V
50 Hz, 230 V
25 A
32 A
3 × Min. 2.5
3 × Min. 4
3 × 1.5 (Polar)
3 × 1.5 (Polar)
1 × Min. 1.5
1 × Min. 1.5
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
230 VAC
230 VAC
230 VAC
230 VAC
24 VDC
24 VDC
12 VDC
12 VDC
3 poles isolator
SW120V
SW100, 120Y
~/N (single),
3N~ (3 ph 4-wires),
50 Hz, 230 V
50 Hz, 400 V
40 A
3 × Min. 6
5 × Min. 1.5
3 × 1.5 (Polar)
3 × 1.5 (Polar)
1 × Min. 1.5
1 × Min. 1.5
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
230 VAC
230 VAC
24 VDC
12 VDC
S1
Indoor Unit
(Interface unit /
S2
Flow temp.
controller)
S3
16 A
230 VAC
230 VAC
24 VDC
12 VDC
9

Publicité

Table des Matières
loading

Table des Matières