WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Safety notes
Safety extra low voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area.
- Keep away People from the operating area of the
drive
- Keep away children from the control.
- Observe pressure load diagram of the toothed rack!
- Use only in dry rooms
- Only for inside mounting
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Use option "-W" in case of outside mounting!
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r ed safety slip!
Pressure load diagram
Maximum pressure load of the toothed rack is not automatically identical with maximum pressure force of the drive!
At the DXD 150-BSY+ (-HS) loads of more than 1000
N up to 1500 N are transient admissible only (e.g.
prior to snow removal or in case of wind loads).
These may occur up to a stroke of 1750 mm.
DXD 150-BSY+ (-HS)
3500
3000
2500
2000
1500
1000
500
0
6/16
DXD-BSY+ (-HS)
durable
temporary
Stroke (mm)
Intended use
- Rack and pinion drive for electric opening and
closing of heavy windows and flaps in the facade
and roof area
- Operating voltage 24 V DC
- Usheable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Performance features
- micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
8 drives
- individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- closing edge protection for the main closing edge
- especially silent in ventilation operation
because of reduced motor speed
Extent of supply
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
At the DXD 300-BSY+ (-HS) loads of more than 2000
N up to 3000 N are transient admissible only (e.g.
prior to snow removal or in case of wind loads).
These may occur up to a stroke of 1500 mm.
3500
3000
2500
2000
1500
1000
500
0
English
DXD 300-BSY+ (-HS)
durable
temporary
Stroke (mm)
99.824.27 1.4/05/18