INSTALLATION, RELOCATION AND INSPECTION

Installation place
Avoid installing the air conditioner in the following places.
• Where ß ammable gas could leak.
CAUTION:
Do not install the unit where ß ammable gas could leak.
If gas leaks and collects around the unit, it may cause
an explosion.
• Where there is much machine oil.
• Salty places such as the seaside.
• Where sulÞ de gas is generated such as a hot spring.
• Where oil is splashed or where the area is Þ lled with
oily smoke.
• Where there is high-frequency or wireless equipment.
WARNING:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since
there may be a refrigerant leak. Be sure to ask the service representative whether there is refrigerant leakage or not
when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas
leaks indoors, and comes into contact with the Þ re of a fan heater, space heater, stove, etc., harmful substances will
be generated.
Electrical work
• Provide an exclusive circuit for the power supply of the air conditioner.
• Be sure to observe the breaker capacity.
WARNING:
• The customer should not install this unit.
If installation is done incorrectly, it may cause a Þ re, an electric shock, or injury from the unit falling, water leaking,
etc.
• Do not use intermediate connection of the power supply cord or the extension cord and do not connect many
devices to one AC outlet.
A Þ re or an electric shock may result from poor contact, poor insulation, exceeding the permissible current, etc.
Consult your dealer.

SPECIFICATIONS

Set name
Model
Indoor
Outdoor
Function
Cooling
Power supply
Capacity
kW
Input
kW
Indoor
kg
Weight
Outdoor
kg
Refrigerant Þ lling
kg
capacity (R410A)
Indoor
IP code
Outdoor
Permissible
LP ps
MPa
excessive
operating
HP ps
MPa
pressure
Indoor (Super High/
dB(A)
48/44/38/32
High/Med./Low)
Noise level
Outdoor
dB(A)
14
The installation location of the outdoor unit should be at
least 3 m away from the antennas for TV sets, radios, etc.
In areas where the reception is weak, provide greater space
between the outdoor unit and the antenna of the affected
Inverter-type
device if operation of the air conditioner interferes with radio
ß uorescent lamp
To prevent the effects
or TV reception.
of a ß uorescent lamp,
keep as far apart as
possible.
Keep a space
to prevent the
picture
distortion or
the noise.
100 mm or
1 m or
more
more
TV
1 m or
more
Cordless
phone or
Portable
phone
3 m
or more
Radio
MSZ-GB50VA
MSZ-GB50VA
MUZ-GB50VA
Heating
~/N, 230V, 50Hz
5.0
5.8
1.65
1.70
9
53
1.50
IP 20
IP 24
1.64
4.15
48/42/36/30
52
55
CAUTION:
• Earth the unit.
Do not connect the earth to a gas pipe, water pipe, lightning rod or the earth of a telephone. If the earthing is
incorrect, it may cause an electric shock.
Wall, etc.
• Install an earth leakage breaker depending on the place where the air conditioner is to be installed (humid places,
etc.).
Well-ventilated
dry place
If the earth leakage breaker is not installed, it may cause an electric shock.
Inspection and maintenance
200 mm or
more
• When the air conditioner is used for several seasons, the capacity may be lowered due to dirt inside the unit.
• Depending on the condition, an odor may be generated or dehumidiÞ ed water may not drain out smoothly due to dirt,
dust, etc.
• It is recommended that the unit be inspected and maintained (charged) by specialist in addition to normal maintenance.
Consult your dealer.
Operating sound considerations
• Do not put an object around the air outlet of the outdoor unit. This may lower the capacity or increase the volume of the
operating sound.
• If an abnormal sound is heard during operation, consult your dealer.
Relocation
• When the air conditioner is to be removed or re-installed because of rebuilding, moving, etc., special techniques and work
are required.
WARNING:
Repairs or relocation should not be done by the customer.
If this is done incorrectly, it may cause a Þ re, an electric shock, or an injury from the unit falling, water leaking, etc.
Consult your dealer.
Disposal
To dispose of this product, consult your dealer.
NOTE:
1. Rating condition
Cooling — Indoor:
27°C DB, 19°C WB
Outdoor: 35°C DB
Heating — Indoor:
20°C DB
Outdoor: 7°C DB, 6°C WB
2. Guaranteed operating range
Indoor
32°C DB
Upper limit
23°C WB
Cooling
21°C DB
Lower limit
15°C WB
27°C DB
Upper limit
Heating
20°C DB
Lower limit
If you have any questions, consult your dealer.
Outdoor
43°C DB
-10°C DB
24°C DB
18°C WB
-10°C DB
-11°C WB