ELECTRICAL AND CONTROL SETTINGS
5.4 WIRING SIZE AND MINIMUM REQUIREMENTS OF THE PROTECTION DEVICES
!
C A U T I O N
Check to ensure that the field supplied electrical components
(mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical
data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to
standards, rules, regulations, etc.
Use a dedicated power circuit for the indoor unit. Do not use a power
circuit shared with the outdoor unit or any other appliance.

Outdoor unit

Model
RAS-4WHVNPE
RAS-5WHVNPE
RAS-6WHVNPE
RAS-4WHNPE
RAS-5WHNPE
RAS-6WHNPE
Indoor unit alone
Power
Model
supply
RWH-4.0VNFE
1~
RWH-5.0VNFE
230V
50Hz
RWH-6.0VNFE
RWH-4.0NFE
3N~
RWH-5.0NFE
400V
50Hz
RWH-6.0NFE
?
N O T E
The data corresponding to DHW tank heater is calculated in combination with the YUTAKI S80 domestic hot water tank accessory "DHWT-(200/300)
S-3.0H2E".
16
PMML0340B rev.1 - 03/2016
Max.
Power supply
current
(A)
20
1~ 230V 50Hz
25
25
14
3N~ 400V 50Hz
14
16
Operation mode
Without simultaneous operation
of electric heater in DHW tank
With simultaneous operation of
electric heater in DHW tank
Without simultaneous operation
of electric heater in DHW tank
With simultaneous operation of
electric heater in DHW tank
Without simultaneous operation
of electric heater in DHW tank
With simultaneous operation of
electric heater in DHW tank
Without simultaneous operation
of electric heater in DHW tank
With simultaneous operation of
electric heater in DHW tank
Without simultaneous operation
of electric heater in DHW tank
With simultaneous operation of
electric heater in DHW tank
Without simultaneous operation
of electric heater in DHW tank
With simultaneous operation of
electric heater in DHW tank
?
N O T E
Electric fuses can be used instead of magnetic Circuit Breakers (CB).
In that case, select fuses with similar rated values as the CB.
The Earth Leakage Breaker (ELB) mentioned on this manual is also
commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
The Circuit Breakers (CB) are also known as Thermal-Magnetic
Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Use wires which are not lighter than the polychloroprene
sheathed flexible cord (code designation 60245 IEC 57).
Transmitting
Power supply cables
EN60335-1
EN60335-1
2 x 4.0 mm² + GND
2 x 6.0 mm² + GND
2 x 6.0 mm² + GND
2 x 0.75 mm
4 x 2.5 mm² + GND
4 x 2.5 mm² + GND
4 x 4.0 mm² + GND
Power supply
Max.
cables
current
(A)
EN60335-1
24
2 x 6.0 mm² + GND
38
2 x 10.0 mm² + GND
28
2 x 6.0 mm² + GND
42
2 x 10.0 mm² + GND
31
2 x 6.0 mm² + GND
45
2 x 10.0 mm² + GND
10
4 x 2.5 mm² + GND
24
2 x 4.0 mm² + GND
10
4 x 2.5 mm² + GND
24
2 x 4.0 mm² + GND
10
4 x 2.5 mm² + GND
24
2 x 4.0 mm² + GND
CB
cables
(A)
(nº of poles/A/mA)
20
25
25
2
15
15
20
Transmitting
cables
CB
(A)
EN60335-1
32
40
32
50
32
50
2 x 0.75 mm
2
15
25
15
25
15
25
ELB
2/40/30
4/40/30
ELB
(nº of
poles/A/
mA)
2/40/30
2/63/30
2/40/30
2/63/30
4/40/30