Insulating The Refrigerant Tubing; Taping The Tubes; Finishing The Installation; How To Install The Remote Controller (Optional Part) - Panasonic S-28MD1E5 Instructions D'installation

Masquer les pouces Voir aussi pour S-28MD1E5:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 25
SUPPLEMENT
If the flare nuts are over-tightened, the flare may be
damaged, which could result refrigerant leakage and cause
in injury or asphyxiation to room occupants.
● For the flare nuts at tubing connections, be sure to use the
flare nuts that were supplied with the unit, or else flare nuts
for R410A (type 2). The refrigerant tubing that is used must
be of the correct wall thickness as shown in the table.
Tightening torque,
Tube diameter
Tube thickness
approximate
14 – 18 N · m
ø6.35 (1/4")
0.8 mm
(140 – 180 kgf · cm)
34 – 42 N · m
ø9.52 (3/8")
0.8 mm
(340 – 420 kgf · cm)
49 – 61 N · m
ø12.7 (1/2")
0.8 mm
(490 – 610 kgf · cm)
68 – 82 N · m
ø15.88 (5/8")
1.0 mm
(680 – 820 kgf · cm)
100 – 120 N · m
ø19.05 (3/4")
1.0 mm
(1000 – 1200 kgf · cm)
Because the pressure is approximately 1.6 times higher than
conventional refrigerant pressure, the use of ordinary flare
nuts (type 1) or thin-walled tubes may result in tube rupture,
injury, or asphyxiation caused by refrigerant leakage.
● In order to prevent damage to the flare caused by over-
tightening of the flare nuts, use the table above as a guide
when tightening.
● When tightening the flare nut on the liquid tube, use an
adjustable wrench with a nominal handle length of 200 mm.

5-3. Insulating the Refrigerant Tubing

Tubing Insulation
● Thermal insulation must be applied to all unit tubing,
including distribution joint (purchased separately).
Two tubes arranged together
Liquid tubing
Gas tubing
Insulation
Fig. 5-7
* For gas tubing, the insulation material must be heat
resistant to 120°C or above. For other tubing, it must be
heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH
70%, increase the thickness of the gas tubing insulation
material by 1 step.
CAUTION
If the exterior of the outdoor unit valves has been finished
with square duct covering, make sure you allow sufficient
space to use the valves and to allow the panels to be
attached and removed.
N OTE
Gas Leakage Detector
Note that the gas leakage detector should be capable of
detecting the refrigerant R410A.
Air Purging
Refer to "AIR PURGING" in the separate Installation
Instructions for the outdoor unit in regard to air purging with a
vacuum pump (for test run) preparation.
Taping the fl are nuts
Cover up the tubing connections with the supplied flare
insulator. Then fasten the insulator at both ends with the vinyl
clamps (field supply).
Insulation material
The material used for insulation must have good insulation
characteristics, be easy to use, be age resistant, and must not
easily absorb moisture.
Never grasp the drain or refrigerant connecting outlets
when moving the unit.
CAUTION
After a tube has been insulated, never try to bend it into
a narrow curve because it can cause the tube to break or
crack.

5-4. Taping the Tubes

(1) At this time, the refrigerant tubes (and electrical wiring if
local codes permit) should be taped together with armoring
tape in 1 bundle. To prevent the condensation from
overflowing the drain pan, keep the drain hose separate
from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you
wrap the tubing, overlap half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1 clamp approx.
each meter. (Fig. 5-8)
Clamp
Insulated tubes
Drain hose
Fig. 5-8

NOTE

Do not wind the armoring tape too tightly since this will
decrease the heat insulation effect. Also ensure that the
condensation drain hose splits away from the bundle and drips
clear of the unit and the tubing.
35

5-5. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering. (Fig. 5-9)
Apply putty here
Tubing
Fig. 5-9
6. HOW TO INSTALL THE REMOTE
CONTROLLER (OPTIONAL PART)
NOTE

Refer to the Operating Instructions attached to the optional

Remote Control Unit.

7. HOW TO INSTALL THE CEILING PANEL

■ 1-Way Cassette Type (D1 Type)

Component Parts
Unit: mm
Part name
Quantity
Appearance
Ceiling panel
1
(2P, yellow)
Used for
Short-circuit
1
high ceiling installation
connector
M
5 × 40
Washer-head
4
screw
4 × 12
Screw
2
For fastening
side panel
4 × 35
Screw
2
For fastening front/rear
center of panel

7-1. Installing the Panel on the Indoor Unit

7-1-1. Removing the intake grille
(1) Remove the 2 screws that fasten each of the 2 grilles in
place. (Fig. 7-1)
(2) Slide the intake grille hooks (2 locations) in the direction of
the arrow to open the intake grille. (Fig. 7-1)
(3) When the intake grille is open, use a flathead (minus)
screwdriver to press on the rear hinge tabs (2 locations),
then remove the intake grille. (Fig. 7-1)
Press on the
tabs with a
flathead (minus)
screwdriver
while pulling out
Hinge
the intake grille.
Slide
Hook
Intake grille
Fig. 7-1
7-1-2. Removing the side panels
1
(1) Slide the side panels in the direction of the arrow
remove them (2 locations, left and right). (Fig. 7-2)
1
Slide
Side panel
Slide tabs
Fig. 7-2
7-1-3. Installing the ceiling panel
(1) Fasten the hooks on both sides of the ceiling panel to
the indoor unit. The hooks on one side (2 locations) are
stationary, while the hook on the other side is movable.
(Fig. 7-3)
(2) Place the panel at a slight angle, and fasten the panel
stationary hooks onto the hook receivers on the side of the
indoor unit.
(3) After verifying that the hooks are fastened, press the other
side of the panel up so that it is level. Press up until the
movable hook has fastened to the hook receiver on the
indoor unit.
(4) Verify that the hooks on both sides of the ceiling panel
have been securely fastened before removing your hands.
At this point the panel is provisionally attached to the
indoor unit.
● When removing the panel, press the movable hook toward
the inside while being careful to support the panel.
(Fig. 7-4)
Press to remove.
Hook receiver
Stationary hooks
Movable hook
Fig. 7-4
Fig. 7-3
Movable hook
(5) Align the panel installation holes with the screw holes in
the indoor unit.
(6) Fit the supplied washer-head screws into the 4 panel
installation holes, and tighten them until the panel is tightly
attached to the indoor unit. (Fig. 7-5)
36
to

Publicité

Table des Matières
loading