How To Process Tubing; Connecting The Refrigerant Tubing; Connecting Tubing Between Indoor And Outdoor; Units - Panasonic S-28MD1E5 Instructions D'installation

Masquer les pouces Voir aussi pour S-28MD1E5:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 25
K1 type (22, 28, 36 types)
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.
Protective ground screw (External Solenoid
Valve Kit for 3WAY)
L1 L2
N U1 U2
Power Supply
Remote Control Wiring
Inter-unit Control Wiring
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)
P1, R1 types
Protective ground screw
(External Solenoid Valve Kit for 3WAY)
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.
Remote Control Wiring
Power Supply
Inter-unit Control Wiring
SUPPLEMENT
K1 type (46, 56, 73, 106 types)
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)*
Protective ground screw
(External Solenoid Valve Kit for 3WAY)*
Fixture screw for resin cover
Resin cover
R1
R2
L1
L2
N
U1
U2
Inter-unit Control Wiring
Power Supply
Remote Control Wiring
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.
* As to functional ground screw and protective ground screw,
remove the fixture screw and resin cover. Then, carry out
earth ground work.
33

5. HOW TO PROCESS TUBING

5-1. Connecting the Refrigerant Tubing

Use of the Flaring Method
Many of conventional split system air conditioners employ the
flaring method to connect refrigerant tubes which run between
indoor and outdoor units. In this method, the copper tubes are
flared at each end and connected with flare nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 30 – 50 cm longer
than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a tube
reamer or file. This process is important and should be
done carefully to make a good flare. Be sure to keep
any contaminants (moisture, dirt, metal filings, etc.) from
entering the tubing. (Figs. 5-1 and 5-2)
Deburring
Before
After
Fig. 5-1
NOTE
When reaming, hold the tube end downward and be sure that
no copper scraps fall into the tube. (Fig. 5-2)
Copper
tubing
Reamer
Fig. 5-2
(3) Remove the flare nut from the unit and be sure to mount it
on the copper tube.
(4) Make a flare at the end of copper tube with a flare tool.
(Fig. 5-3)
Flare nut
Copper
tubing
Flare tool
Fig. 5-3
NOTE
A good flare should have the following characteristics:
● inside surface is glossy and smooth
● edge is smooth
● tapered sides are of uniform length
Caution Before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent dust or
water from entering the tubes before they are used.
(2) Be sure to apply refrigerant lubricant (ether oil) to the
surface of a flare before making piping connections.
Pay attention not to attach the oil to the surface of screw.
This is effective for reducing gas leaks. (Fig. 5-4)
Apply refrigerant
lubricant
Fig. 5-4
(3) For proper connection, align the union tube and flare tube
straight with each other, then screw in the flare nut lightly
at first to obtain a smooth match. (Fig. 5-5)
Flare nut
Union
Fig. 5-5
● Adjust the shape of the liquid tube using a tube bender at the
installation site and connect it to the liquid tubing side valve
using a flare.
Cautions During Brazing
● Replace air inside the tube with nitrogen gas to prevent
copper oxide film from forming during the brazing
process. (Oxygen, carbon dioxide and Freon are not
acceptable.)
● Do not allow the tubing to get too hot during brazing.
The nitrogen gas inside the tubing may overheat,
causing refrigerant system valves to become damaged.
Therefore allow the tubing to cool when brazing.
● Use a reducing valve for the nitrogen cylinder.
● Do not use agents intended to prevent the formation
of oxide film. These agents adversely affect the
refrigerant and refrigerant oil, and may cause damage or
malfunctions.

5-2. Connecting Tubing Between Indoor and Outdoor

Units

(1) Tightly connect the indoor-side refrigerant tubing extended
from the wall with the outdoor-side tubing.
(2) To fasten the flare nuts, apply specified torque.
Indoor Unit Tubing Connection (
,
...
)
1
2
n-1
Indoor unit type
22
28
36
45
56
73
106
Gas tubing (mm)
ø12.7
ø15.88
Liquid tubing (mm)
ø6.35
ø9.52
● When removing the flare nuts from the tubing connections,
or when tightening them after connecting the tubing, be sure
to use two adjustable wrenches or spanners as shown. (Fig.
5-6)
Torque wrench
Spanner
Indoor unit
Outdoor unit
Fig. 5-6
34

Publicité

Table des Matières
loading

Table des Matières