Measurement error with constant level
Fault description
1. Measured value
shows a too low or too
high level
2. Measured value
Fault description
3. Measured value re-
mains in the area of the
4. Measured value re-
mains momentarily
-
ing and then jumps to
the correct level
5. Measured value
jumps sporadically to
6. Measured value
0 m distance
Error pattern
Reason
Min./max. adjustment not
correct
Incorrect linearisation curve
Running time error (small meas-
Due to the process, the
amplitude of the product echo
decreases
A false signal suppression was
not carried out
Amplitude or position of a
false signal has changed (e.g.
buildup); false signal suppres-
sion no longer matches
Error pattern
Reason
Echo from the probe end larger
than the product echo, for exam-
oil-based, solvents, etc.
Turbulence on the product
0
time
Changing condensation or
contamination on the probe
0
time
Level echo is no longer detected
in the close range due to false
signals in the close range. The
tion mode. The max. level (0 m
distance) as well as the status
are outputted.
10 Diagnostics and servicing
Adapt min./max. adjustment
Adapt linearisation curve
Repeat setup
Carry out a false signal suppres-
sion
Determine the reason for the
changed false signals, carry out
false signal suppression, e.g.
with buildup
Check parameter "Medium"
and "Vessel height", adapt if
< 2.5
necessary
r
Check parameters, change if
necessary, e.g. in dosing vessel,
reactor
Carry out a false signal suppres-
sion
Eliminate false signals in the
close range
Check installation conditions
-
-
65