ALL OPERATIONS DESCRIBED IN THIS SECTION MUST BE PERFORMED BY QUALIFIED PERSONNEL
ONLY.
Our Company assumes no liability for damages caused by incorrect connections or operations not
contained in this manual.
BEFORE INSTALLING THE UNIT, READ THE PROVIDED "INSTALLATION INSTRUCTIONS".
THE UPS HAS WHEEL FOR HANDLING; MAKE SURE THE CABLES ARE LONG ENOUGH TO ALLOW THE
UPS TO BE MOVED FOR MAINTENANCE
I

NSTALLATION ENVIRONMENT

The UPS is able to operate at a temperature between 0 and 40°C. The recommended operating
temperature for the UPS and the batteries is between 20 and 25°C. The actual operating life of the batteries
is 5 years on average at an operating temperature of 20°C. If the operating temperature reaches 30°C, the
operating life is halved.
natural ventilation
forced ventilation
air conditioning system,

INSTALLATION

-
UP
"Installation Instructions"
Installation Instructions
- 66 -