PROBLEM
THE DISPLAY SHOWS
C05
THE DISPLAY SHOWS
A01
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A30, A32, A33, A34
THE UPS WILL NOT
START UP
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F09, F10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A08, A09, A10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F42, F43, F44, L42, L43,
L44
POSSIBLE CAUSE
MANUAL BYPASS SWITCH
(SWMB) CLOSED
NO JUMPER ON TERMINALS
FOR REMOTE MAINTENANCE
BYPASS (See "In/Out
connection access")
INCORRECT DATA
CONFIGURATION
INCORRECT DATE AND
TIME
INCORRECT MINIMUM
AUTONOMY SETTING
INCORRECT MAXIMUM
BATTERY CHARGER
CURRENT SETTING
AMBIENT
TEMPERATURE < 0°C
DISSIPATOR TEMPERATURE
SENSOR FAULT (DISSIPATOR
TEMPERATURE < 0°C)
UPS INPUT STAGE
MALFUNCTION
Phase1 VOLTAGE MUCH
LOWER THAN THE OTHER
TWO PHASES.
(VOLTAGE IMBALANCE)
INSERTION OF ABNORMAL
LOADS
UPS INPUT OR OUTPUT
STAGE MALFUNCTION
NO CONNECTION ON ONE OR
MORE PHASES
FUSES BROKEN INSIDE
PROTECTIONS ON INPUT
PHASES
FUSES BROKEN INSIDE
PROTECTIONS ON
BATTERIES
- 98 -