ALLTRONIC SEMIS Série Manuel D'installation page 45

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

PROBLEMA
IL DISPLAY INDICA C05
IL DISPLAY INDICA A01
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
A30, A32, A33, A34
E L'UPS NON PARTE
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F09, F10
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
A08, A09, A10
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F42, F43, F44, L42, L43,
L44
POSSIBILE CAUSA
SEZIONATORE BYPASS
MANUALE (SWMB) CHIUSO
MANCA IL PONTICELLO SUI
MORSETTI PER BYPASS
MANUTENZIONE REMOTO
(Vedi "Accesso collegamenti
In/Out")
CONFIGURAZIONE DATI
ERRATA
DATA E ORA NON
CORRETTA
ERRATA IMPOSTAZIONE
AUTONOMIA MINIMA
ERRATA CONFIGURAZIONE
CORRENTE MASSIMA
CARICABATTERIE
TEMPERATURA
AMBIENTE < 0°C
MALFUNZIONAMENTO DEL
SENSORE DI TEMPERATURA
SUL DISSIPATORE
(TEMPERATURA DEL
DISSIPATORE < 0°C)
MALFUNZIONAMENTO NELLO
STADIO DI INGRESSO
DELL'UPS
LA FASE 1 PRESENTA UNA
TENSIONE MOLTO MINORE
DELLE ALTRE DUE FASI.
(SBILANCIAMENTO DELLE
TENSIONI)
INSERIMENTO DI CARICHI
ANOMALI
MALFUNZIONAMENTO DELLO
STADIO DI INGRESSO O DI
USCITA DELL'UPS
MANCANZA DEL
COLLEGAMENTO SU UNA O
PIÙ FASI
ROTTURA DEI FUSIBILI
INTERNI DI PROTEZIONE
SULLE FASI DI INGRESSO
ROTTURA DEI FUSIBILI
INTERNI DI PROTEZIONE
SULLE BATTERIE
- 46 -
SOLUZIONE

Publicité

Table des Matières
loading

Produits Connexes pour ALLTRONIC SEMIS Série

Ce manuel est également adapté pour:

Semis 160Semis 200

Table des Matières