Symbols
Meaning
Q
Reactive power of the system
Q = Q1 + Q2 + Q3
Q1
Reactive power phase 1
(phase-to-neutral L1 – N)
Q2
Reactive power phase 2
(phase-to-neutral L2 – N)
Q3
Reactive power phase 3
(phase-to-neutral L3 – N)
S
Apparent power of the system
S = √ I
+ I
2
1
2
S1
Apparent power phase 1
(phase-to-neutral L1 – N)
S2
Apparent power phase 2
(phase-to-neutral L2 – N)
S3
Apparent power phase 3
(phase-to-neutral L3 – N)
Sr
Rated value of the apparent power of the
system
PF
Active power factor cosϕ = P/S
PF1
Active power factor phase 1
PF2
Active power factor phase 2
PF3
Active power factor phase 3
Reactive power factor sin ϕ = Q/S
QF
QF1
Reactive power factor phase 1
QF2
Reactive power factor phase 2
QF3
Reactive power factor phase 3
LF
Power factor of the system
LF = sgnQ · (1 – PF)
LF1
Power factor phase 1
sgnQ1 · (1 – PF1)
LF2
Power factor phase 2
sgnQ2 · (1 – PF2)
LF3
Power factor phase 3
sgnQ3 · (1 – PF3)
c
Factor for the intrinsic error
R
Output load
Rn
Rated burden
H
Power supply
Hn
Rated value of the power supply
CT
c.t. ratio
VT
v.t. ratio
MODBUS
is a registered trademark of Schneider Automation Inc.
®
· √ U
+ I
+ U
+ U
2
2
2
2
2
3
1
2
3
P1/S1
P2/S2
P3/S3
Q1/S1
Q2/S2
Q3/S3
MODBUS
(Bus interface RS-485)
®
Connections:
GND on pin 2d
Tx- / Rx- on pin 6z
Tx+ / Rx+ on pin 6d
(see Fig. 5)
Connecting cable:
Screened twisted pairs
Max. distance:
Approx. 1200 m (approx. 4000 ft.)
Baudrate:
1200 ... 9600 Bd (programmable)
Number of bus station: 32 (including master)
Dummy load:
Not required
Input
Waveform:
Sinusoïdal
Rated frequency:
Acc. to type label
50, 60 or 16 2/3 Hz
Own consumption [VA]
(with external
Voltage circuit: ≤ U
power supply):
Current circuit: ≤ I
Continuous thermal ratings of inputs
Current circuit
10 A 400 V
Voltage circuit
480 V single-phase AC system
831 V three-phase system
Short-time thermal rating of inputs
Input
Number
variable
of
inputs
Current circuit 400 V single-phase AC system
693 V three-phase system
100 A
5
250 A
1
Voltage circuit 1 A, 2 A, 5 A
Single-phase
AC system
600 V
H
: 1.5 Ur
10
intern
Three-phase
1040 V
H
: 1.5 Ur
10
intern
/ 400 kΩ
2
· 0.01 Ω
2
single-phase AC system
693 V
three-phase system
Duration
Interval
of
between two
overload
overloads
3 s
5 min.
1 s
1 hour
10 s
10 s
10 s
10 s
37