5. Commissioning, operation

5. Commissioning, operation
Personnel: Skilled personnel
Before installation, commissioning and operation, ensure that the appropriate instrument has
been selected in terms of scale range, design and specific measuring conditions.
EN
WARNING!
Physical injuries and damage to property and the environment caused by
hazardous media
Upon contact with hazardous media (e.g. with flammable or toxic substances),
harmful media (e.g. corrosive, toxic, carcinogenic, radioactive), there is a danger
of physical injuries and damage to property and the environment.
Should a failure occur, aggressive media with extremely high temperature and
under high pressure may be present at the instrument.
For these media, in addition to all standard regulations, the appropriate exist-
ing codes or regulations must also be followed.
Wear the requisite protective equipment.
WARNING!
Physical injuries and damage to property and the environment caused by
media escaping under high pressure
With the pressurisation of the instrument, as a result of poor sealing of the
process connection, media under high pressure can escape.
Due to the high energy of the media that can escape in the event of a failure, the
possibility of physical injuries and damage to property exists.
The sealing of the process connection must be carried out expertly and
checked for leak tightness.

5.1 Mechanical connection

In accordance with the general technical regulations for pressure gauges (e.g. EN 837-2
"Selection and installation recommendations for pressure gauges").
Instruments must be grounded via the process connection. This is why electrically conduc-
tive sealing should be used at the process connection. Alternatively, take other measures for
grounding. Measures for grounding applied ex works (e.g. welding spots or fuse plates) must
therefore be used to integrate the instruments into the equipotential bonding system and
must not be removed under any circumstances. Ensure that the measures for grounding are
reinstalled after dismounting (e.g. replacing the instrument).