Using the inverter
➤ If this happens, shut down the inverter with the main switch (fig. 5 3,
page 4).
➤ Check that the inverter is sufficiently ventilated and that the ventilation
grilles are unimpeded.
➤ Wait 5 – 10 minutes and switch the inverter on again without any electric
consumers.
When operating the inverter at high load for lengthy periods, it is advisable to
start the engine in order to recharge the vehicle battery.
10.3

Configuring the inverter

You can adjust the device using the DIP switch (fig. 5 1, page 4).
Setting the mains voltage
You can set the mains voltage using the S1 and S2 dip switches.
Mains voltage
200 V
220 V
230 V
240 V
Setting the mains frequency
!
WARNING! Danger of electrocution
Only adjust the S3 DIP switch when the respective frequency for
the output voltage should be used.
You can set the mains frequency using the S3 dip switch.
Net frequency
50 Hz
60 Hz
50
DIP switch
S1
Off
On
Off
On
DIP switch
S3
Off
On
SinePower
S2
Off
Off
On
On