Intended use
- Chain drive for electric opening and closing of
windows and flaps in the facade and roof area
- By VdS is the maximum load for the chain
at pressure = 600 mm and at tension = 1000 mm
- Operating voltage 24 VDC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Safety notes
Operating voltage 24 VDC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- This product may not be operated without the
covering stoppers, which are delivered with
bracket sets
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed red safety slip!
Functional description
A synchron-group (KA-BSY+) can be count up to 8
drives, which communicate by a bus. Each drive has
it's own adress. This adress is configurable with SCS
software.
The last drive of a synchron-group is the master,
which controls the other drives, the slaves. Different
forces between the drives of a group will balanced
with intelligent force- and position control. In case of
malfunction respective cutoff of a drive, all drives will
shut down from the master-drive.
Extent of supply
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
6/20
KA-BSY+
Performance features
- Microprocessor controlled synchro electronics
BSY + for a precise synchronous run of up to
8 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Power supply and BSY+ signal can be looped
through: with KA 34-BSY+ for max. 3 drives, with
KA 54-BSY+ for max. 2 drives
- Power supply is possible from both sides
- Locking relief after closing
Pressure load diagram
Observe maximum pressure load of the chain!
Maximum pressure load of the chain is not
automatically identical with maximum pressure force
of the drive!
500
400
300
200
100
0
KA 54-BSY+
Dimensions
40 mm
English
Stroke / (mm)
KA 34-BSY+
A
Stroke
250
195,5
350
247,5
500
322,5
600
372,5
700
422,5
800
472,5
900
526,5
1000
576,5
1100
628,5
1200
678,5
1300
728,5
99.823.89 2.4/12/13
B
369
421
496
546
596
646
700
750
802
852
902