Outdoor Unit Installation - Mitsubishi Electric MXZ-2C20NAHZ2 Notice D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1-5. INSTALLATION DIAGRAM
Open as a rule
More than 19-11/16
in. (500 mm) if the
front and both sides
are open
More than
3-15/16 in.
(100 mm)
Open as a rule
More than 19-11/16 in. (500 mm) if the
bac , both sides and top are open

Outdoor unit installation

6-7/8
Air inlet
Air inlet
2 - (15/32 × 1-31/32)
o al holes ( ase bolt M10)
2. OUTDOOR UNIT INSTALLATION
2-1. INSTALLING THE UNIT
e sure to x the unit's legs with bolts when installing it.
e sure to install the unit rmly to ensure that it does not fall by an earthqua e or a gust.
Refer to the gure in the right for concrete foundation.
In case of MXZ-2C20NA Z2, MXZ-3C24/30NA Z2, do not use the drain soc et and the drain caps.
In case of MXZ-5C42NA2, do not use the drain soc et and the drain caps in the cold region. Drain may freeze and it ma es the fan stop.
Ma e the setting
depth deeper.
En-3
After the lea test, apply insulat-
ing material tightly so that there
is no gap.
When the piping is to be attached to
a wall containing metals (tin plated)
or metal netting, use a chemically
treated wooden piece 25/32 in. (20
mm) or thic er between the wall
and the piping or wrap 7 to 8 turns
of insulation
the piping.
To use existing piping, perform
COOL operation for 30 minutes
and pump down before remo ing
the old air conditioner. Rema e are
according to the dimension for new
refrigerant.
More than 3-15/16 in. (100 mm)
More than 7-7/8 in. (200 mm)
if there are obstacles to both
sides
More than 13-25/32 in.
(350 mm)
2-U-shape notched holes
37-13/32
( ase bolt M10)
23-5/8
Air outlet
Unit : inch
Fix here with
M10 bolts.
Ma e with wider.
PARTS TO BE PROVIDED AT YOUR SITE
(A) Power supply cord*
( ) Indoor/outdoor unit connecting wire*
(C) Extension pipe
(D) Wall hole co er
(E) Piping tape
Extension drain hose (or soft P C
(F)
hose, 19/32 in. (15 mm) inner
inyl tape around
diameter or hard P C pipe P16)
( ) Refrigeration oil
( ) Putty
(I) Pipe xing band
(J) Fixing screw for (I)
( ) Wall hole slee e
* Note:
Place indoor/outdoor unit connecting wire ( ) and
power supply cord (A) at least 3 ft. (1 m) away from
the T antenna wire.
The
to be used per indoor unit.
Units should be installed by licensed contractor according to
local code requirements.
Outdoor unit installation
950
175
600
Air inlet
Air inlet
Air outlet
2 - 12 × 36
o al holes ( ase bolt M10)
23-5/8
Anchor leg
(600)
Anchor bolt length
Anchor bolt pitch
(Unit: inch (mm))
amount
2 to 7
2 to 7
'ty for ( ) to ( ) in the abo e table is quantity
2-U-shape notched holes
( ase bolt M10)
Unit : mm
1
1
1
1
1
1
Little
1
1