5. Fan Motor Drive Circuit
Microcomputer
No. of
rotation output
No. of
rotation detect
The waveform of
voltage at the
point
The waveform of
voltage at the
point
The waveform of
voltage at the
point
The 15.7 kHz PWM pulse shown in Fig. 5-2 from the micro-
computer pin
changes with instruction number of rotations.
This pulse changes to analog voltage by R751 and C751 and it is
applied to the fan motor as instruction voltage number of
rotations. The relationship between the voltage of point
number of rotations becomes as shown in Fig. 5-3. (The gap may
arise depending on the condition of unit.)
The feedback pulse of number of rotation is outputted from the
fan motor and input to micro computer pin
this pulse is 12/60 of the number of rotations. (Ex: 1000min
12/60=200Hz) The microcomputer observes this frequency and to
make it as the instruction number of rotation all the time, adjusts
the output pulse width of pin
If the feedback pulse becomes lower than 100min
lock or failure of a fan motor, the fan output stops temporary as
the fan lock is faulty. The pulse will output again after 10 seconds.
If the abnormal in fan lock is detected twice in 10 minutes, the
unit is completely stopped and change to the fault mode which
the timer lamp blinks 10 times.
Downloaded from
www.Manualslib.com
A
40
R751
C751
0V
14
C631
C
0V
T1
T2
At T2
At T1
T1
T2
is output to point
. The width of this pulse
40
14
.
40
manuals search engine
CN10
35V line
0V
5V line
B
R631
Fig. 5-1
T1 = Low No. of rotation
T2 = High No. of rotation
Fig. 5-2
and
. The frequency of
(about 1200)
-1
X
-1
( min
-1
caused by
– 75 –
6
4
M
3
2
Fan Motor
1
)
0
2
4
1
3
Voltage of point
(V)
B
Fig. 5-3
5