11 Device Information

1
Type and order code
2
Design
2.1
Model
2.2
Degree of protection according to EN 60 529
for compact devices and heating components
2.3
Installation Location
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
Cooling, flow
Air (heating)
Air (cooling)
3.2
Temperature spread
of heating water
3.3
Heat output / COP
3.4
Temperature spread
of cooling water
3.5
Cooling capacity / COP
3.6
Sound power level
3.7
Sound pressure level at a distance of 10m
3.8
Heating water flow with an internal pressure differential of m³/h / Pa
3.9
Cooling water flow with an internal pressure differential of m³/h / Pa
3.10 Air flow rate with an external static pressure differential of m³/h / Pa
3.11 Refrigerant; total filling weight
3.12 Lubricant; total filling weight
4
Dimensions, connections and weight
4.1
Device dimensions
4.2
Device connections to heating system
4.3
Weight of the transportable unit(s) incl. packing
5
Electrical connection
5.1
Nominal voltage; fuse protection
5.2
Nominal power consumption
5.3
Starting current with soft starter
5.4
Nominal current
5.5
max. power consumption of compressor protection
(per compressor)
6
Complies with the European safety regulations
7
Additional model features
7.1
Defrosting
Type of defrosting
Defrosting tray included
7.2
Heating water in device protected against freezing
7.3
Performance levels
7.4
Controller internal/external
1. See operating limits diagram
2. This data indicates the size and capacity of the system according to EN 255 and EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters,
such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following
meaning: 2 °C external air temperature and 55 °C heating water flow temperature.
3. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35°C.
4. See CE declaration of conformity
5. The heat circulating pump and the heat pump manager must always be ready for operation.
EN-8
1
°C / °C
°C
°C
°C
at A2 / W35
2
at A-7 / W35
kW / ---
2
at A-7 / W45
kW / ---
2
at A2 / W35
kW / ---
2
at A2 / W50
kW / ---
2
at A7 / W35
kW / ---
2
at A7 / W45
kW / ---
2
at A10 / W35
kW / ---
at A35 / W7
at A27 / W7
kW / ---
at A27 / W18
kW / ---
at A35 / W7
kW / ---
at A35 / W18
kW / ---
dB(A)
type / kg
type / litres
H x W x L cm
Inch
kg
V / A
2
A2 W35
kW
A
A2 W35 / cos 
A / ---
W
LA 11ASR
Reversible
IP24
Outdoors
Up to 58 / above 18
+7 to +20
-25 to +35
+15 to +40
9.7
5.0
7.1 / 2.9
6.6 / 2.7
6.4 / 2.3
8.8 / 3.2
8.8 / 3.1
8.5 / 2.5
11.3 / 3.8
11.3 / 3.6
9.6 / 3.1
12.2 / 4.1
12.1 / 3.9
6.5
5.0
8.8 / 2.8
8.8 / 2.8
10.9 / 3.3
10.8 / 3.2
7.6 / 2.1
7.5 / 2.1
9.5 / 2.5
9.5 / 2.5
63
33
1.0 / 3000
1.3 / 10900
1.0 / 3000
1.9 / 5900
2500
R404A / 5.1
Polyolester / 1.5
136 x 136 x 85
G 1'' external
241
400 / 16
2.74
2.84
23
4.9 / 0.8
5.2 / 0.8
70
4
Automatic
Reverse cycle
Yes (heated)
5
Yes
1
External
LA 16ASR
Reversible
IP24
Outdoors
Up to 58 / above 18
+7 to +20
-25 to +35
+15 to +40
9.3
5.0
10.6 / 3.0
10.5 / 2.9
9.9 / 2.5
12.8 / 3.4
12.7 / 3.2
12.0 / 2.5
15.1 / 3.8
14.9 / 3.6
14.7 / 3.3
16.7 / 4.1
16.6 / 3.9
6.6
5.0
12.6 / 2.6
12.5 / 2.6
16.4 / 2.8
16.4 / 2.8
10.7 / 2.0
10.6 / 2.0
14.3 / 2.3
14.3 / 2.2
64
34
1.4 / 4500
2.6 / 14600
1.4 / 4500
1.8 / 7000
4000
R404A / 5.7
Polyolester / 1.9
157 x 155 x 85
G 1'' external
289
400 / 20
3.8
4
25
6.9 / 0.8
7.2 / 0.8
70
4
Automatic
Reverse cycle
Yes (heated)
5
Yes
1
External