Technical Data; Accessories - S+S Regeltechnik Premasgard 1210 Notice D'instruction

Convertisseur de pression et de pression différentielle, y compris kit de raccordement, forme compacte, avec raccordement modbus
Masquer les pouces Voir aussi pour Premasgard 1210:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASGARD
Quality product for HVAC sector, accuracy ± 1.5 % or ± 3 %
The calibrateable PREMASGARD
measuring above-atmospheric, below-atmospheric, or differential pressures of air. The piezo-resistive measuring element is temperature-compensated
and guarantees high reliability and accuracy. The pressure transmitters are provided with a pushbutton for manual zero point calibration and an adjust-
able offset. Applications of these pressure sensors are in cleanroom, medical and filter technology, at ventilation and air conditioning ducts, at spray
booths, in large-scale catering facilities, for filter monitoring and level measurement, or for triggering frequency converters. Media measured with
these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media. These differential pressure sensors
are supplied including connection set ASD -06 (2 m connection hose, two pressure connection nipples, screws).

TECHNICAL DATA:

Power supply: .......................... 24 V AC (± 20 %) and 15 ... 36 V DC (± 10 %)
Power consumption: ................. < 1 VA ⁄ 24 V DC, < 2,2 VA ⁄ 24 V AC
Measuring ranges: ................... – 1000...+ 1000 Pa, or
Bus interface: ......................... RS 485, galvanically isolated,
Bus protocol: ......................... Modbus (RTU mode)
Baud rate: .............................. 9600, 19200, 38400 Baud
Status indicator: ..................... LED green = Telegram valid
Media temperature: ................. 0 ... + 50 °C
Pressure connection: ............... 4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
Type of pressure: ...................... differential pressure
Medium: ................................. clean air and other non-aggressive, non-combustible gases
Accuracy: ............................... ± 1.5 % or ± 3 % EW (at 20°C)
Zero point offset: .................... ± 10 % of pressure range end value
Above- ⁄ below-
atmospheric pressure: ............. max. 5 x pressure range end value
Long-term stability:................. ± 1 % per year
Hysteresis: ............................ 0.3 % of final value
Media contacting parts: ........... brass, Ni, Nylon, PU, Si
Temperature drift values: ......... ± 0.1 % of final value ⁄ °C
Current consumption: .............. < 20 mA
Linearity: .............................. < ± 1 % of final value
Enclosure: ............................. plastic, material polyamide, 30 % glass-globe-reinforced,
Enclosure dimensions: ............. 72 x 64 x 37.8 mm (Thor III without display)
Cable gland: ........................... M 16 x 1.5 , including strain relief, exchangeable,
Electrical connection: .............. 0.14 - 1.5 mm², via terminal screws
Humidity: .............................. < 95 % r. H., non-precipitating air
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity, electromagnetic compatibility according to
Features: .............................. illuminated single line display, cutout ca. 36 x15 mm (W x H),
ACCESSORIES: ....................... including connection set ASD-06 (nipple straight)
1210
®
1210 series compact pressure sensors with Modbus connection are optionally equipped with display and are used for
– 5000...+ 5000 Pa,
depending on the type of device, see table
Bus termination activatable via DIP switches.
Up to 32 devices possible in one segment.
In case of a greater number of devices, RS485 transceivers must be used.
address range 0...247 selectable
LED red = Telegram error
metal pressure connection nozzles
depending on the type of device
with quick-locking screws (slotted ⁄ Phillips head combination),
colour pure white (similar RAL 9010), enclosure cover for display is transparent!
72 x 64 x 43.3 mm (Thor III with display)
max. inner diameter 10.4 mm
EN 61 326 + A1 + A2, EMC directive 2004 ⁄ 108 ⁄ EC
to display ACTUAL pressure
(included in the scope of delivery)
connection nipple ASD-07 (at 90 degree angle)
pressure outlet DAL-1 for ceiling or in-wall installation (e.g. in clean rooms)
10

Publicité

Table des Matières
loading

Table des Matières