Technical Data; Accessories - S+S Regeltechnik PREMASREG DS 2 Notice D'instruction

Masquer les pouces Voir aussi pour PREMASREG DS 2:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASREG
  DS 2
The mechanical differential pressure switch ⁄ differential pressure monitor PREMASREG
monitoring above-atmospheric, differential and below- atmospheric pressures of clean air and other gaseous, non-aggressive non-combus-
tible media in air ducts, air intake or exhaust devices, as pressure difference detector or pressure monitor for flow detection at electric
heating registers, for monitoring V-belts and filters, as air pressure deficiency protection, for observation of fans and air dampers, or
as limit value controller. Switchpoint adjustment is done internally at an inside precision scale. These instruments are factory-calibrated.
The differential pressure switch PREMASREG
connection nipples, screws).
TECHNICAL DATA:
Switching capacity: .................... 5 (0.8) A, 250 V AC
(Contact load)
Contact: ....................................... single-pole potential-free changeover contact,
Pressure range: ......................... see table
Enclosure: .................................... base: material PC (10 % GF),
Temperature of medium: .......... - 30 °C ...+ 85 °C
Membrane: .................................. silicone, LSR (Liquid Silicon Rubber, tempered at 200 °C,
Humidity: ...................................... < 90 % r. H., non-precipitating air
Electrical connection: ................ 0.14 - 1.5 mm
Pressure connection: ................ P1 (+) for higher pressure
Mounting: ..................................... by 4-hole base ring, plastic  (included in the scope of delivery),
Protection class: ........................ II (according to EN 60 730)
Protection type:.......................... IP 54 (according to EN 60529) with top cover in place
Standards: ................................... CE conformity, low-voltage directive 73 ⁄ 23 ⁄ EEC
Tests: ............................................ DVGW (according to DIN 1854), VDE 0630, EN 61058,
FUNCTION: ................................. Contact 1 - 2 breaks when pressure ⁄ differential pressure
ACCESSORIES: .......................... including connection set ASD - 06 (nipple straight) and
Type ⁄ WG2 
Pressure Range 
DS - 205 F
20...300 Pa
DS - 205 B
50...500 Pa
DS - 205 D
100...1000 Pa

Accessories:

ASD - 06 connection set (included in the scope of delivery), consisting of
2 connection nipples (straight) made of ABS, 2 m PVC hose, soft, and 4 tapping screws
ASD - 07 connection nipples (at 90 degree angle) made of plastic, ABS
®
DS-2 is supplied including connection set ASD-06 (2 m connection hose, two pressure
4 (0.7) A, 30 V DC
multi-layer contact, gold-plated (DDC compatible)
colour light grey (similar RAL 7035),
top cover: material PC, transparent,
sheet steel mounting angle, cable gland PG 11
non-outgassing, LABS-free, no emission of varnish adhesion
inhibiting substances)
2
, via terminal screws on circuit board
P2 ( - ) for lower pressure
Ø 6.2 mm (nipples)
mounting position vertical (factory setting)
directive on gas devices 90 ⁄ 396 ⁄ EEC, CE 0085 A P 0918
rises to the preset value.
Contact 1- 3 closes when pressure ⁄ differential pressure
drops and can be used as signal contact.
mounting ring DS2-MR (included in the scope of delivery)
connection nipple ASD - 07 (at 90 degree angle) optional
(Adjustable) 
(0.2 mbar...3.0 mbar)
(0.5 mbar...5.0 mbar)
(1.0 mbar...10.0 mbar)
®
DS-2 with 4-hole plastic base ring is used for
Operating Difference ca. 
0.1 mbar + ⁄ - 15 %
0.2 mbar + ⁄ - 15 %
0.4 mbar + ⁄ - 15 %
Max. Pressure
5000 Pa (50 mbar)
5000 Pa (50 mbar)
5000 Pa (50 mbar)