6000-5040-0000-1XX 50400-2021 V101 03 ⁄ 2021
716x - VA
PREMASREG
®
D
Bedienungs- und Montageanleitung
Druck-Messumformer ⁄ -Schalter ⁄ -Wächter
für Volumenstrom, Differenzdruck,
Filterüberwachung und Flüssigkeits-Niveauerfassung
G
Operating Instructions, Mounting & Installation
Pressure measuring transducer ⁄ swtich ⁄ control switch
for volume flow, differential pressure,
filter monitoring and liquid level detection
F
Notice d'instruction
Convertisseur de mesure de pression ⁄ pressostat
pour débit volumique, pression différentielle,
contrôle de filtrage et détection de niveau de liquide
r
Руководство по монтажу и обслуживанию
Измерительный преобразователь ⁄ реле давления ⁄
реле контроля давления для объемного расхода,
разности давлений, контроля работы фильтров и
измерения уровня жидкости
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS - STR. 22
90411 NÜRNBERG ⁄ GERMANY
FON +49 ( 0 ) 911 ⁄ 5 19 47- 0
mail@SplusS.de
www.SplusS.de
®
PREMASREG
716x - VA
LCD
®
PREMASREG
716x - VAQ
LCD
CARTONS
ET EMBALLAGE
PAPIER À TRIER

Publicité

loading

Sommaire des Matières pour S+S Regeltechnik PREMASREG 716x-VA

  • Page 1 Измерительный преобразователь ⁄ реле давления ⁄ реле контроля давления для объемного расхода, разности давлений, контроля работы фильтров и измерения уровня жидкости S+S REGELTECHNIK GMBH THURN-UND-TAXIS - STR. 22 90411 NÜRNBERG ⁄ GERMANY CARTONS FON +49 ( 0 ) 911 ⁄ 5 19 47- 0 ET EMBALLAGE mail@SplusS.de...
  • Page 2 D G F r 716x - VA PREMASREG ® Maßzeichnung ® PREMASREG 716x - VA Dimensional drawing Plan coté Габаритный чертеж Schnell-Steckanschluss (standardmäßig) Quick connect (standard) Raccord rapide (de série) Быстроразъемное (в качестве стандартного оснащения) M20x1.5 M20x1.5 M20x1.5 M20x1.5 M20x1.5 Rohrverschraubung (optional) Pipe fitting...
  • Page 3 ® PREMASREG 716x - VA Rev. 2021 - V13 Der elektronische Drucksensor und -schalter PREMASREG ® 716x - VA ist mit Messfunktionen für Volumenstrom, Differenzdruck, Filterüberwachung und Flüssigkeits-Niveauerfassung auf Basis der Druckmessung in sauberer Luft ausgestattet. Die Geräte mit Gehäuse aus Edelstahl V4A, mit Kabelverschraubung oder M12-Steckverbinder nach DIN EN 61076-2-101 und Druckanschluss mittels Schnell-Steck-Verbindung aus Edelstahl (Rohrverschraubung optional) enthalten einen schaltenden Ausgang, einen stetigen Ausgang und ein hintergrundbeleuchtetes Display zur Einstellung des Schaltpunktes und Anzeige der IST-Werte.
  • Page 4 ® PREMASREG 716x - VA Rev. 2021 - V13 Schaltbild ® 3-Leiter- ® PREMASREG 716x - U ⁄ W PREMASREG 716x - U ⁄ W Anschluss SET-Einstellung 230V AC Schaltpunkt Relais Taster Zeit Auto Zero (optional) Nullpunkt setzen 24V AC/DC DOWN SELECT AUTO ZERO...
  • Page 5 ® PREMASREG 716x - VA Funktionstypen Montageschema Volumenstrom V = k · √∆ p = Volumenstrom in m = k-Faktor 1...3000 ∆ p = Differenzdruck in Pa Differenzdruck ∆ p = p – p – ∆ p = Differenzdruck in Pa = höherer Druck = niedriger Druck –...
  • Page 6 ® PREMASREG 716x - VA Einstellen des Offsets: ® PREMASREG 716x (MB: 0...+ xx Pa) Nach erfolgreicher Nullpunktkalibrierung beträgt die Ausgangsspannung (bei Mittelstellung des Offsetreglers) DOWN DOWN DOWN DOWN AUTO ZERO AUTO ZERO AUTO ZERO AUTO ZERO SELECT SELECT SELECT SELECT 0 V bei O Pa Druckdifferenz! min.
  • Page 7 ® PREMASREG 716x - VA Anzeige im Display: Konfiguration der Messfunktion: Im Display wird in der ersten Zeile der gemessene IST-Wert für Volumenstrom, Druck, Verschmutzungsgrad oder Niveau angezeigt. DOWN DOWN AUTO ZERO AUTO ZERO SELECT SELECT In der zweiten Zeile wird die entsprechende Einheit min.
  • Page 8 ® PREMASREG 716x - VA Einstellen der Parameter Typ 0: Volumenstrom k-Faktor von 1 bis 3000 EBM-PAPST Je nach Hersteller werden die k-Faktoren ZIEHL-ABBEG / 0,7746 unterschiedlich berechnet. Daher ist es GEBHARDT / 0,7746 notwendig die jeweilige Berechnungs formel ROSENBERG bei der Eingabe heranzuziehen: = 3600 / k FLÄKT...
  • Page 9 Wichtige Hinweise Wichtige Hinweise Die Einbaulage ist beliebig. Der Spannungsausgang ist kurzschlussfest, ein Anlegen einer Überspannung am Spannungsausgang zerstört das Gerät. Die Druckbereiche (Messbereiche) sind auf dem Geräteetikett angeben. Bei Messdrücken außerhalb dieses Bereiches kommt es zu Fehlmessungen, zu erhöhten Abweichungen oder es kann zur Zerstörung des Druckmessumformer führen. –...
  • Page 10 ® PREMASREG 716x - VA Rev. 2021 - V13 The electronic PREMASREG ® 761x - VA pressure sensor and switch is equipped with measuring functions for volume flow, differential pressure, filter monitoring and liquid level detection based on pressure measurement in clean air. The devices with a housing made from stainless steel V4A, with cable gland or M12 connector according to DIN EN 61076-2-101 and pressure port by stainless steel quick connect (pipe fitting optional) are fitted with one switching output, one continuous output and a backlit display for setting the switching point and displaying the ACTUAL values.
  • Page 11 ® PREMASREG 716x - VA Rev. 2021 - V13 Schematic diagram ® 3-wire- ® PREMASREG 716x - U ⁄ W PREMASREG 716x - U ⁄ W connection SET-Setting 230V AC switchpoint relay Pushbutton Zero point setting time Auto Zero (optional) 24V AC/DC SELECT DOWN...
  • Page 12 ® PREMASREG 716x - VA Function types Mounting diagram Volume flow rate V = k · √∆ p = Volume flow in m = K factor 1...3000 ∆ p = Differential pressure in Pa Differential pressure ∆ p = p – p –...
  • Page 13 ® PREMASREG 716x - VA Setting the offset: ® PREMASREG 716x (Range: 0...+ xx Pa) After successful zero point calibration, the output voltage is 0 V at 0 Pa pressure difference DOWN DOWN DOWN DOWN AUTO ZERO AUTO ZERO AUTO ZERO AUTO ZERO SELECT SELECT...
  • Page 14 ® PREMASREG 716x - VA Display readout: Configuring the measuring function: The first line of the display shows the measured ACTUAL value for volume flow rate, pressure, contamination degree, or level. DOWN DOWN AUTO ZERO AUTO ZERO SELECT SELECT The second line shows the corresponding unit min.
  • Page 15 ® PREMASREG 716x - VA Setting the parameters: Type 0: Volume flow rate K factor from 1 to 3000 EBM-PAPST Depending on the manufacturer, the K ZIEHL-ABBEG factors are calculated differently. Therefore, / 0.7746 GEBHARDT it is necessary to use the corresponding / 0.7746 ROSENBERG calculation formula to enter data:...
  • Page 16 General notes This device can be mounted in any position. The voltage output is short-circuit proof. Applying overvoltage at the voltage output will destroy this device. Pressure ranges are indicated on the device label. Applying measuring pressures beyond that range will cause mismeasurements and increased deviations or may destroy the device.
  • Page 17 ® PREMASREG 716x - VA Rev. 2021 - V13 Le capteur de pression et pressostat électronique PREMASREG ® 716x - VA est équipé de fonctions de mesure pour le débit volumique, la pression différentielle, le contrôle de filtrage et la détection de niveau de liquide, basées sur la mesure de la pression de l'air propre. Les appareils avec boîtier en acier inox V4A, avec presse-étoupe ou connecteur M12 selon DIN EN 61076-2-101 et raccord de pression avec raccord rapide en acier inoxy- dable (raccord fileté...
  • Page 18 ® PREMASREG 716x - VA Rev. 2021 - V13 Schéma de raccordement ® 3 fils ® PREMASREG 716x - U ⁄ W PREMASREG 716x - U ⁄ W raccordement SET-Setting 230V AC switchpoint relay Pushbutton Zero point setting time Auto Zero (optional) 24V AC/DC SELECT DOWN...
  • Page 19 ® PREMASREG 716x - VA Types de fonction Schéma de montage Débit volumique V = k · √∆ p = débit volumique en m = k-facteur 1...3000 ∆ p = pression différentielle en Pa Pression différentielle ∆ p = p – p –...
  • Page 20 ® PREMASREG 716x - VA Réglage de l'offset : ® PREMASREG 716x (plage de mesure: 0...+ xx Pa) Une fois le calibrage du point zéro effectué, le courant de sortie (si le bouton offset est en position médiane) DOWN DOWN DOWN DOWN AUTO ZERO AUTO ZERO...
  • Page 21 ® PREMASREG 716x - VA Affichage à l’écran : Configuration de la fonction de mesure : La première ligne de l'écran affiche la valeur effective pour le débit volumique, la pression, le degré d'encrassement ou le niveau. DOWN DOWN AUTO ZERO AUTO ZERO SELECT SELECT L'unité...
  • Page 22 ® PREMASREG 716x - VA Réglage des paramètres : Type 0: débit volumique Facteur k de 1 à 3000 EBM-PAPST Les facteurs k sont calculés différemment en ZIEHL-ABBEG fonction du fabricant. C'est pour cette raison / 0,7746 GEBHARDT qu'il est nécessaire de tenir compte de la formule / 0,7746 ROSENBERG de calcul correspondante lors de la saisie :...
  • Page 23 Généralités La position de montage peut être choisie librement. La sortie en tension est isolée de la masse, l’application d’une surtension à la sortie en tension causerait la destruction de l’appareil. Les plages de pression (plages de mesure) sont indiquées sur l’étiquette signalétique de l’appareil. Le non-respect des dites plages de mesure entraînera des mesures erronées, des incertitudes de mesure plus élevées ou peut causer la destruction du convertisseur de pression.
  • Page 24 ® PREMASREG 716x - VA Rev. 2021 - V13 Электронный датчик и реле давления PREMASREG ® 716x - VA служат для измерения объемного расхода, разности давлений и уровня жидкости, а так же контроля работы фильтров на основании измерения давления в чистом воздухе. Эти устройства скорпусом из высококачественной стали V4A, с...
  • Page 25 ® PREMASREG 716x - VA Rev. 2021 - V13 Схема подключения ® Трехпроводное ® PREMASREG 716x - U ⁄ W PREMASREG 716x - U ⁄ W схеме SET-Setting 230V AC switchpoint relay Pushbutton Zero point setting time Auto Zero (optional) 24V AC/DC SELECT DOWN...
  • Page 26 ® PREMASREG 716x - VA Types de Типы функций Схема монтажа Объемный расход V = k · √∆ p = объемный расход в м /ч = коэффициент  К 1...3000 ∆ p = разность давлений в Па Разность давлений ∆ p = p –...
  • Page 27 ® PREMASREG 716x - VA Установка смещения: ® PREMASREG 716x (диапазон измерения: 0...+ xx Па) После успешной калибровки положения нуля выходное напряжение (в среднем положении регулятора смещения) DOWN DOWN DOWN DOWN AUTO ZERO AUTO ZERO AUTO ZERO AUTO ZERO SELECT SELECT SELECT SELECT составляет...
  • Page 28 ® PREMASREG 716x - VA Индикация на дисплее: Конфигурация функции измерения: В первой строке дисплея отображается фактическое значение объемного расхода, давления, степени загрязнения или уровня. DOWN DOWN AUTO ZERO AUTO ZERO SELECT SELECT Во второй строке показывается соответствующая min. max. min.
  • Page 29 ® PREMASREG 716x - VA Настройка параметров: Тип 0: Объемный расход Коэффициент k от 1 до 3000 EBM-PAPST В зависимости от производителя коэффициенты ZIEHL-ABBEG k рассчитываются по-разному. Поэтому при / 0,7746 GEBHARDT вводе следует применять соответствующую / 0,7746 ROSENBERG формулу расчета: = 3600 / k FLÄKT Единица...
  • Page 30 Указания к продуктам Установочная длина может быть любой. Выход напряжения защищен от короткого замыкания, приложение завышенного напряжения к выходу напряжения выводит прибор из строя. Диапазоны давлений (диапазоны измерения) указаны на этикетке/табличке прибора. Попытка измерения давления вне этих пределов ведет к погрешностям, повышенным отклонениям или может стать причиной выхода из строя измерительного преобразователя давления. –...