Replacing the frequency converter
If the frequency converter has been replaced, proceed as follows:
•
login as Admin
•
press the Kongskilde logo in the upper right corner for 10 sec
•
The Kongskilde logo changes to LOAD MOTOR DATA and flashes
•
press the flashing LOAD MOTOR DATA
•
on the new page press: Load parameters to drive
•
when the blue bar is at 100%, press Return
The software is now downloaded to the frequency converter.
In the event that it is not possible to load the new data, the frequency con-
verter is not set up to communicate via the Profinet connection.
In the Supply Voltage field, you can change the parameters of the supply
voltage to the frequency converter, e.g. if the mains supply is 480V. This is
only necessary in case of repeated overvoltage faults when operating the
blower. See section "Troubleshooting" if necessary.
In the event that it is not possible to load the new data, the frequency con-
verter is not set up to communicate via the Profinet connection.