Toshiba RAV-SM2244AT7 Manuel D'installation page 17

Masquer les pouces Voir aussi pour RAV-SM2244AT7:
Table des Matières
Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 27
Digital Inverter
Adding additional refrigerant
Figure of Simultaneous twin
Outdoor Unit
Formula for calculating the amount of additional refrigerant
(Formula will differ depending on the diameter of the liquid connecting side pipe.)
* 1 to 7 are the lengths of the pipes shown in the figures above (unit: m).
Simultaneous twin
Diameter of connecting pipe
(liquid side)
1
2
Ø12.7
Ø9.5
Simultaneous triple
Diameter of connecting pipe (liquid side)
1
2
Ø12.7
Ø9.5
Simultaneous double twin
Diameter of connecting pipe
Outdoor
unit
1
SM2244
Ø12.7
SM2804
Ø12.7
All manuals and user guides at all-guides.com
Indoor Unit
Indoor Unit
2
3
1
Figure of Simultaneous double twin
Indoor Unit
Outdoor Unit
4
Amount of additional
refrigerant per meter
(g/m)
α
3
Ø9.5
80
3
4
Ø9.5
Ø9.5
Amount of additional
(liquid side)
refrigerant per meter (g/m)
α
2, 3
4 to 7
Ø9.5
Ø6.4
80
Ø9.5
Ø9.5
80
Figure of Simultaneous triple
Indoor Unit
Outdoor Unit
Indoor Unit
Indoor Unit
5
6
2
3
1
Amount of additional refrigerant (g) =
Amount of refrigerant added for main pipe +
amount of refrigerant added for branch piping
β
α × ( 1 – 28) + β × ( 2 + 3 – 4)
40
Amount of additional
Amount of additional refrigerant (g) =
refrigerant per meter
Amount of refrigerant added for main pipe +
(g/m)
amount of refrigerant added for branch
α
β
80
40
Amount of refrigerant added for main pipe
β
γ
40
20
40
40
16
Indoor Unit
Indoor Unit
4
2
3
1
Indoor Unit
7
piping
α × ( 1 – 28) + β × ( 2 + 3 + 4 – 6)
Amount of additional refrigerant (g) =
+ amount of refrigerant added for first
branch piping + amount of refrigerant
added for second branch piping
α × ( 1 – 28) + β × ( 2 + 3 – 4) +
γ × ( 4 + 5 + 6 + 7)
α × ( 1 – 28) + β × ( 2 + 3 – 4) +
γ × ( 4 + 5 + 6 + 7)
EN