HSI 90/HSI 150. How to set in concrete correctly.
3 Description: Single wall insert HSI 90/HSI 150-K/X
For setting in concrete. Single-sided connection of HSI 90/HSI 150 system covers, HRD press seals or
KES-M 90/KES-M150 cable entry systems on the outside of the building.
Fig.: HSI 150-K/X
*Protective foil
Connection
side
*Protective foil not shown in subsequent
pictures!
When installing single wall inserts, the square frame (connection side) must be installed on the
outside of the building.
HSI 150-GSM single wall insert with plug-in socket
For setting in concrete. For connecting smooth plastic cable ducts with �
the outside of the building/shaft. Single-sided connection of HSI 150 system covers, HRD press seals
on the inside of the building/shaft (we recommend HRD 150/160-G(-WE)-z/d for HSI 150-GSM110/X
or HSI 150-GSM125/X).
Fig.: HSI 150-GSM160/X
Quality
seal
If a cable conduit must be at the outside is connected to a wall insert with a plug-in socket,
the socket side or the plug-in socket must sit on the outside of the building or shaft when
setting in concrete.
Reducing the diameter of duct/conduit connections (DN110 or DN125 with system HSI 150 or
DN 75 with system HSI 90) restricts the sealing technology for thick cables.
Intermediate pipe
Assembly frame
Blind cover
HSI 150-D
Rubber plug-in
socket with 3-ribbed
seal
Pipe cover
Assembly frame
Blind cover
HSI 150-D
11
= 110, 125 or 160 mm on