Electrical Wiring

Connection method of the connecting cable (Example)

1. Make a hole appropriate for the passage of connection cable through on cap by tool.
2. After knocking out the holes, we recommend you paint the edges and areas around the edges using
the repair paint to prevent rusting
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with the cord clamp providing on the unit not to have strain at the terminal.
6. Finally, Fix the cap to the conduit panel.
Model name
Conduit (inch)
Knockout Diameter (inch)
WARNING
• Loose wiring may cause the terminal to overheat or result in unit malfunction.
• A fire hazard may also exist.
• Therefore, be sure all wiring is tightly connected.
46
Outdoor Unit
Conduit
AWG
ARUN038GS2
8
3/4
1-3/32
ARUN048GS2
8
3/4
1-3/32