Bulk LED off
Absorption LED
off
flashing
off
0
3
flashin
1
4
g
on
2
5
Bulk LED
Code
Absorption LED
Float LED
Device is switched off because
1
one of the other phases in the
3
expected devices were found in
No other device whatsoever
4
5
System time synchronisation
10
14
Device cannot transmit data.
One of the devices has assumed
17
18
This device cannot function as
22
Switch-over system protection
24
Firmware incompatibility. The
firmware of one the connected
25
devices is not sufficiently up to
date to operate in conjunction
26
22
Bulk LED flashes
On
6
off
flashin
7
g
8
on
Meaning:
system has switched off.
Not all, or more than, the
the system.
detected.
Overvoltage on AC-out.
problem occurred.
'master' status because the
original master failed.
Overvoltage has occurred.
'slave'.
initiated.
with this device.
Internal error.
Absorption LED
off
flashing
on
9
12
15
10
13
16
11
14
17
Cause/solution:
Check the failing phase.
The system is not properly configured. Reconfigure the
system.
Communication cable error. Check the cables and switch all
equipment off, and then on again.
Check the communication cables.
Check the AC cables.
Should not occur in correctly installed equipment. Check the
communication cables.
Check the communication cables (there may be a short
circuit).
Check the failing unit. Check the communication cables.
Check AC cables.
This device is an obsolete and unsuitable model. It should be
replaced.
Should not occur in correctly installed equipment. Switch all
equipment off, and then on again. If the problem recurs,
check the installation.
Possible solution: increase lower limit of AC input
voltage to 210VAC (factory setting is 180VAC)
1) Switch all equipment off.
2) Switch the device returning this error message on.
3) Switch on all other devices one by one until the error
message reoccurs.
4) Update the firmware in the last device that was switched
on.
Should not occur. Switch all equipment off, and then on
again. Contact Victron Energy if the problem persists.