Télécharger Imprimer la page

LEGRAND DAKER DK Plus Serie Manuel D'installation page 38

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
4 Setting
INDICATION
This chapter is valid for all the UPSs of the Daker DK Plus series excluding the 3-1 version 3 101 78.
If the UPS is connected to one or more battery cabinets, it is necessary to set their number to fore-
cast a realistic backup time. This can be done from the display of the UPS or by using the software
"UPS Setting tool". The UPS must be in standby mode (mains connected to the UPS input).
Follow this procedure to change the UPS settings:
- press simultaneously
twice;
- scroll the different settings pressing
- select the number of battery cabinets installed by pressing
- after changing settings, scroll to the "End" screen and then press
- the UPS restarts automatically. However, it is also suggested to remove the mains for at least 30
seconds.
PARAMETER
NUMBER OF
BATTERY
CABINETS
END SCREEN
and
for approximately three seconds, until the buzzer sounds
until the setting "Battery" is visualized;
SETTING
1-9
Select the number
of battery cabinets
connected to the UPS
ATTENTION
This parameter cannot be
set on the UPS 10 kVA
3 101 78
Press
to save all
changes
DAKER DK Plus
Battery Cabinets
;
to save all changes;
DISPLAY
31

Publicité

loading

Ce manuel est également adapté pour:

Daker dk plus 5000vaDaker dk plus 6000va