Télécharger Imprimer la page

DAB MCE-30/C Instructions Pour L'installation Et La Maintenance page 33

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 40
8.1.2
Regulation with Constant Curve
H
Max.
Min.
Q
8.1.3
Regulation with Constant Curve with External Analogue Signal
H
Max.
Q
Min.
8.1.4
Regulation with Proportional Differential Pressure
8.1.5
T constant function
This function causes the circulator to increase or decrease the flow rate to keep constant the temperature measured by the NTC
sensor, connected as described in paragraph 5.5.3.
Four operating modes can be set:
T Regulation:
Increasing mode T if the desired temperature (Ts) is higher than the measured temperature (T), the circulator increases the flow
rate until Ts is reached
Decreasing mode T if the desired temperature (Ts) is higher than the measured temperature (T), the circulator decreases the flow
rate until Ts is reached
T1 Regulation:
Increasing mode T1 if the desired temperature (Ts) is higher than the measured temperature (T1), the circulator increases the flow
rate until Ts is reached
Decreasing mode T1 if the desired temperature (Ts) is higher than the measured temperature (T1), the circulator decreases the
flow rate until Ts is reached
8.1.6
∆T-costant function
This feature allows the circulator to increase or decrease the flow rate to keep the temperature difference T-T1 constant in absolute
value.
There are 2 setpoints: dTs1, dTs2 and, therefore, you can have the following 2 situations:
dTs1 different from dTs2:
-
In this case there are 5 configurable operation intervals in which the dTs setpoint can vary depending on the temperature T or T1 as
shown in the following example:
1)
If T1 ≤ 10°C = > dTs = |T-T1| = 10°C
ENGLISH
The rotation speed is kept at a constant number of revolutions. This rotation speed may be set
between a minimum value and the rated frequency of the circulation pump (e.g. between 15 Hz
and 50 Hz).
This mode may be set by means of the control panel on the cover of the MCE-C (see par. 9).
The rotation speed is kept at a constant number of revolutions in proportion to the voltage of the
external analogue signal (see par. 5.5.2). The rotation speed varies in linear mode between the
rated frequency of the pump when Vin = 10V and the minimum frequency when Vin = 0V.
This mode may be set by means of the control panel on the cover of the MCE-C (see par. 9).
In this adjustment mode the differential pressure is reduced or increased as the water request falls
or rises.
This mode may be set by means of the control panel on the cover of the MCE-C (see par. 9).
30

Publicité

loading

Ce manuel est également adapté pour:

Mce-15/cMce-11/cMce-55/cMce-22/cMce-150/cMce-110/c