5.3
Hybrid menu
Menu item
Bivalent
temperature
Compressor quick
start
Manual defrosting Starts the defrost function for the heat pump compressor.
TC3-TH2 temp.
diff. heat.
Set min. modul.
boiler pump
Low-noise
operation
CH 120 – 6721876580 (2024/02)
Description
Outdoor temperature below which the boiler is switched on.
Starts the heat pump compressor immediately. Depending on
the current boundary conditions, the start of the compressor
may be delayed by a few minutes.
3 ... 7 ... 10 K: temperature difference for control of system
pump PH0
40 ... 100 %. Defines the minimum boiler heating pump speed.
Higher settings ensure greater heating comfort.
Op. mode:
Off: No silent mode
Automatic - reduced output: Operation with set, reduced
output after a time interval
Automatic - heat pump off: Operation without heat pump
after time interval
Low noise mode permanently active: Permanent output
reduction to reduce noise
Start time: Defines the start time of low-noise operation
End time: Defines the end time of low-noise operation
Power reduction: 30 ... 40 ... 60 %: Output of the heat pump
for operation with reduced output
Service menu
15