Service menu
Menu item
Pump connection Appliance: heating pump and heat generator connected.
Mixed HC
Mixer runtime
Type of HC pump Switched: the heating circuit pump runs only with heat demand
Pump error type
Heating system
Max. flow
temperature
Heat control type Weather compensated | Room temp.dependent: selection
Min. outdoor
temperature
Design flow
temperature
12
Description
Module: heating pump and heating circuit module connected
Yes: the heating circuit allocated is a mixed heating circuit
No: the heating circuit allocated is an unmixed heating circuit
10 ... 120 ... 600 s: elapsed time of mixer in the assigned
heating circuit.
Permanent: the heating circuit pump runs continuously
Not used: no alarm circuit is installed.
Normally closed: the alarm circuit closes in the event of a fault.
Normally open: the alarm circuit opens in the event of a fault.
Radiator | Convector | Underfloor: heat exchanger used in the
allocated heating circuit
30 ... 90 °C: Select the flow temperature according to the
heating system
between optimised weather dependent control and room
control as flow temperature control. The weather dependent
control is only available when an outdoor temperature sensor is
connected. If an outdoor temperature sensor is detected
during automatic configuration, Weather compensated is set.
-35 ... -10 ... +10 °C: Minimum outdoor temperature for the
dimensioning of the respective region
30 ... 65 ... 90 °C (example, radiator): The flow temperature
that is reached at the minimum outdoor temperature.