14 EN – USA quick installation guide
Install the drive on the wall
See figure
A
on page 5.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive. Measure the insulation resistance between each phase conductor and
DA
the Protective Earth conductor using a measuring voltage of 500 V DC. The
insulation resistance of an ABB motor must exceed 100 Mohm (reference value at
USA
25 °C or 77 °F). For the insulation resistance of other motors, please consult the
manufacturer's instructions. Note: Moisture inside the motor casing will reduce the
DA
insulation resistance. If moisture is suspected, dry the motor and repeat the
measurement.
DE
ES
ohm
FI
FR
IT
Connect the power cables
NL
See figures
C
1. Remove the front cover. UL Type 1 units: Release the retaining clip with a
PT
screwdriver (a) and lift the cover from the bottom outwards (b).
RU
2. UL Type 1 units: Remove the cable entry box cover by undoing the mounting
screw.
SV
3. Remove the EMC shroud that separates the input and output cabling.
TR
4. Remove the shroud on the power cable terminals by releasing the clips and lifting
the shroud up from the sides with a screwdriver (a). Knock out holes for the
CN
cables to be installed (b).
5. Attach the residual voltage warning sticker in the local language next to the
control board top.
6. Fasten the cable conduits to the cable lead-through plate holes. Strip the cable
ends. Slide the cables through the connectors.
7. Connect the twisted cable shields to the grounding terminals.
U1
M
V1
3~
W1
PE
and D.