10 EN – Quick installation guide
Install the drive on the wall
See figure
A
on page 3.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive. Measure the insulation resistance between each phase conductor and
EN
the Protective Earth conductor using a measuring voltage of 500 V DC. The
insulation resistance of an ABB motor must exceed 100 Mohm (reference value at
DA
25 °C or 77 °F). For the insulation resistance of other motors, please consult the
manufacturer's instructions. Note: Moisture inside the motor casing will reduce the
DE
insulation resistance. If moisture is suspected, dry the motor and repeat the
measurement.
ES
FI
ohm
FR
IT
NL
Connect the power cables
PT
See figures B, C,
1. Remove the front cover. IP21 units: Release the retaining clip with a screwdriver
RU
(a) and lift the cover from the bottom outwards (b).
SV
2. IP21 units: Remove the cable entry box cover by undoing the mounting screw.
3. Remove the EMC shroud that separates the input and output cabling.
TR
4. Remove the shroud on the power cable terminals by releasing the clips and lifting
CN
the shroud up from the sides with a screwdriver (a). Knock out holes for the
cables to be installed (b).
5. Attach the residual voltage warning sticker in the local language next to the
control board top.
6. Cut adequate holes into the rubber grommets. Slide the grommets onto the
cables. Prepare the cable ends. Slide the cables through the holes of the bottom
plate and attach the grommets to the holes.
7. Ground the cable shields 360 degrees under the grounding clamps.
U1
M
V1
3~
W1
PE
D
and E. Use symmetrical shielded cable for the motor cabling.