Télécharger Imprimer la page

Lenze HMI EPM-H521 Instructions De Mise En Service page 55

Publicité

Les langues disponibles

Les langues disponibles

2.2
Electrical data
Field
Display
Display
Clock
Electrical
ect ca
connection
i
Network
et o
Memory
e o y
Interfaces
te aces
EDBPM-H521 DE/EN/FR 2.0
Type
Touch screen
Resolution
Visible size
Lines
Single character size 30 lines at 80 characters each
Double character size 15 lines of 40 characters each
Quadruple character size 7 lines at 20 characters each
Character size
Single character size 2.7 × 5.4 mm, text: 8 × 16 pixels
Double character size 5.4 × 10.7 mm, text: 16 × 32 pixels
Quadruple character size 10.7 × 21.4 mm, text: 32 × 64 pixels
Fonts
Contrast setting
Background illumination
Min. service life at 25°C
Hardware clock
DC voltage supply
Power consumption
Protocol
Communication medium
Network topology
User program (text + graphics)
Data memory (Flash EPROM)
Memory for Windows fonts
Memory card (backup)
Serial MSP (DB25 socket)
Parallel LPT
Technical data
Electrical data
Values
LCD 256 colours TFT
Matrix 40 × 30 (16 × 16 pixels each)
640 × 480 pixels
211.2 × 158.0 mm
Programmable fonts, Windows fonts
Via software
CCFL tube
30000 h
Storage via capacitor,
min. 72 h, typ. 130 h
DC 24 V (+18 ... 32 V)
15 W at DC 24 V
System bus (CAN)
DIN ISO 11898
Line (terminated at both ends with
120 Ω)
960 kB + 6MB
128 kb
512 kb
8 MB
RS232
Centronics
2
55

Publicité

loading

Ce manuel est également adapté pour:

Hmi epm-h521 1a 10