Specifications
Input data for thermocouple (TC)
Sensor
(Standard)
type
B
(DIN 60584-1)
E
(DIN 60584-1)
J
(DIN 60584-1)
K
(DIN 60584-1)
L
(DIN 43710)
N
(DIN 60584-1)
R
(DIN 60584-1)
S
(DIN 60584-1)
T
(DIN 60584-1)
U
(DIN 43710)
W3Re/W25Re (ASTM E988-96)
W5Re/W26Re (ASTM E988-96)
Input resistance
Max. line resistance
Line monitoring
Input error limits
Temperature coefficient
at input
Cold junction compensation
Error of external
cold junction compensation
Error of internal
cold junction compensation
56
Range [°C]
250 ... 1820
-200 ... 1000
-210 ... 1200
-200 ... 1372
-200 ... 900
-200 ... 1300
- 50 ... 1767
- 50 ... 1767
-200 ... 400
-200 ... 600
0 ... 2315
0 ... 2315
> 10 MΩ
1 kΩ
Open circuits
± (10 µV + 0.05% meas.val.)
for spans > 2 mV
50 ppm/K of adjusted end value
(average TC in permitted operating
temp range, reference temp 23 °C)
Internal
Via IrDA: external or fixed value
Via Pt100 for T comp = 0 ... 80 °C:
± (80 mΩ + 0.1% meas.val.)
± 1.5 °C
Selectable via
IrDA only
x
x
x
x
x
x
x
x
x
x