Télécharger Imprimer la page

Knick PolyTrans P32000P0/11-KTA Mode D'emploi page 50

Convertisseurs universels

Publicité

Les langues disponibles

Les langues disponibles

Configuration using Switches
Adjust the DIP and rotary switches according to the table on the
housing.
Sensor type:
Select the connected sensor type using switches DIP1 to DIP3.
Start value:
Adjust the number (00 ... 99) using the "Start" rotary switches.
Adjust the factor using the switches DIP4, DIP5.
To obtain a falling curve, adjust a start value which is higher than the
end value.
End value:
Adjust the number (00 ... 99) using the "End" rotary switches.
Adjust the factor using the DIP6 switch.
Output signals:
Adjust the output signal using the switches DIP7, DIP8.
Note
After completion of configuration you must cover the
switches with the included self-adhesive polyimide tape.
For information on IrDA interface configuration, please refer
to the instruction manual for the Paraly ® SW 111 software
(accessory).
-KTA
FS03
50
Start value (rotary switch)
End value (rotary switch)
DIP S1 (from left to right: 1-8)

Publicité

loading

Ce manuel est également adapté pour:

Polytrans p32000