List displayed:
WRMxx
n.1
SETUP:
|
|
VEoCharge:
14.40V
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VLowBatte:
12.56V
|
|
|
|
VEndLBatt:
auto
|
|
|
|
|
|
Prog.Load:
16hour
|
|
|
|
|
|
VnightThd:
2.00V
|
|
|
MPPT algo:
auto
|
|
|
HrToFloat:
1hour
|
|
IOutMaxCh:
30,21A
UPDATE FW:
---
A
Non presente su WRM20
List displayed:
WRMxx
n.1
SETUP:
not present
Value:
Settable values and description:
<1..24> select te WRMxx to edit.
Set the battery end-of-charge voltage:
Pb Flood 14.80@25°C / 29.60@25°C / 59.20@25°C:
Setting to operate with battery type
Pb Flood.
Pb Seal/Gel 14.40@25°C/ 28.80@25°C / 57.60@25°C:
Setting to operate with battery type
Pb Seal or Gel.
LiFePO4 <14.00..14.70V>
<28.00..29.40V>
<56.00..58.80V> fixed:
Setting to operate with battery type
Lithium with integrated BMS.
11-WBUS Lithium 14.40V / 28.80V / 57.60V fixed:
12-WBUS Lithium 13.50V / 27.00V / 54.00V fixed:
Dedicated setting to operate with smart Lithium
battery.
<12,00..12,56V> / <24,00..25,12V> / <48,00..50,24V> :
below this threshold, the WRMxx goes into
Low Battery status and deactivates the LOAD.
auto(VEoC-0,2/0,4/0,8V);
<12,72..13,68V> / <25,44..27,36V> / <50,88..54,72V> :
above this threshold, the WRMxx goes out
Low Battery status and reactivates the LOAD
24h/24h
<1..16h>
Only Night: LOAD output active only during the night.
Only Day
OnSurPlus : LOAD output active only during a energy surplus.
2,00V; 3,28V; 4,56V; 5,84V : below this threshold the
WRMxx detects the sunset.
auto; parall.; indep. : mode in which the MPPT algorithm
considers the two PV channels.
<1..8h> : duration of the Absorption phase before going
in to the Flaot phase.
<0..30,21A> : maximum charge current per PV channel.
RUN : *CAUTION* starts the procedure to update the
firmware in the WBM device. The firmware update
file must be present in the uSD card.
Value:
Settable values and description:
Device not present.
WRM60 X
User manual
: LOAD output always active.
: LOAD output active from sunset for the set hours.
: LOAD output active only during the day.
27
EN
MENU 8.2
A
A
6
MENU 8.2