The H46C,E Humidity Controllers are used with portable
and central unit dehumidifiers to maintain relative
humidity. The H46 has an spst, snap-acting switch
designed for line voltage circuits. The H46C has two
leadwires for switch box mounting. The H46E has an
electric cord with an interrupter plug.
INSTALLATION
When Installing this Product...
1.
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­
ous condition.
2.
Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3.
Installer must be a trained, experienced service
technician.
4.
After installation is complete, check out product
operation as provided in these instructions.
A CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power supply before connecting
wiring.
Location
Select a location about 5 ft (1.5 m) above the floor in an
area with good circulation at average temperature and
humidity for the area to be controlled. Avoid locations
near hot or cold air ducts and discharge air from the
controlled equipment.
® U .S . R e g i s t e r e d T r a d e m a r k
C o p y r i g h t © 2 0 0 3 H o n e y w e l l I n t e r n a t i o n a l In c .
All manuals and user guides at all-guides.com
H46C,E Humidity Controllers
Mounting H46C
1.
2.
3.
4.
5.
6.
7.
8.
9.
Mounting H46E
1.
2.
3.
4.
NOTE: H46E has a 3-prong plug. When connecting to
• All Rights Reserved
Honeywell
INSTALLATION INSTRUCTIONS
Remove the setting knob.
Pull the cover forward from the device to remove.
Install a 2 in. x 3 in. (51 mm x 76 mm) vertical
switch box at the selected location.
Using the two screws provided, fasten the adapter
plate to the switch box as shown. See Fig. 1.
Pull the wires from the switch box through the
opening in the adapter plate and connect to the
H46 leadwires with the solderless connectors
(provided). See Fig. 4-6 for typical hookups.
Push the wires back into the switch box.
Place the H46 against the adapter plate, making
certain the tab at the bottom of the plate fits into the
notch on the H46.
Fasten the H46 to the adapter plate by tightening
the captive screw.
Replace the cover and the setting knob.
At the selected location, insert the two wood
screws (provided) into the wall 2 in. (51 mm)
vertically apart and protruding 1/16 in. (2 mm) from
the wall. See Fig. 2.
Position the H46 on the screws and slide it down
until the screws are in the slots.
Insert the dehumidifier plug into the end of the
interrupter plug. See Fig. 3.
Insert the interrupter plug into the electrical outlet.
the 2-prong receptacle, use the converter plug
(not included) and connect the pigtail lead to the
ground screw.
6 9 -1 0 0 0 B -1

Publicité

loading

Sommaire des Matières pour Honeywell H46C

  • Page 1 The H46 has an spst, snap-acting switch Using the two screws provided, fasten the adapter designed for line voltage circuits. The H46C has two plate to the switch box as shown. See Fig. 1. leadwires for switch box mounting. The H46E has an Pull the wires from the switch box through the electric cord with an interrupter plug.
  • Page 2 Connections and Operation A dehumidistat in combination with the thermostat can be used to run the air conditioner to control relative humidity levels. The H46C dehumidistat and thermostat can be wired in parallel or in series. • KEYHOLES Wiring in parallel allows the dehumidistat to indepen­...
  • Page 3 PROVIDE O VERLOAD PROTECTIO N AN D DISCONNECT MEANS COIL COIL AS REQUIRED. H EATING DAMPER M OTOR, IF USED. CLOGGED FILTER SW ITCH OR COOLIN G PANEL CONNECTIO N. M7913 Fig. 5. Typical parallel wiring hookup for H46C with T87F/Q539A combination for dehumidification and mildew control. 69-1000B-1...
  • Page 4 All manuals and user guides at all-guides.com H46C,E HUMIDITY CONTROLLERS H46C T87F/Q539A INTERNALSCHEMATIC M7914 Fig. 6. Typical series wiring hookup of H46C with T87F/Q539A combination for dehumidification and mildew control. SETTINGS AND ADJUSTMENT CHECKOUT The H46 makes contact on a relative humidity rise to the After all mounting and wiring is completed, turn on the set point to start the dehumidifier.
  • Page 5 Montage du H46C Enlever le bouton de réglage. 2. Tirer le couvercle vers l’avant pour l’enlever. Les hygrostats H46C,E assurent la commande Installer une boîte de commutation verticale de 51 automatique d’un déshumidificateur autonome ou central x 76 mm (2 x 3 po) à l’endroit choisi.
  • Page 6 Couper l’alimentation avant de raccorder les fils afin EN NYLON d’empêcher les chocs et les dommages à l’équipement. Fig. 1. Montage du H46C sur une boîte de Tout le câblage doit être conforme aux codes et règlements locaux en matière d’électricité. S’assurer que commutation verticale.
  • Page 7 All manuals and user guides at all-guides.com HYGROSTATS H46C,E H46C SCHÉMA INTERNE DE Q539A T87F Fig. 5. Schéma de câblage parallèle type du H46C et du T87F/Q539A pour assurer la déshumidification et empêcher le développement de moisissure. •1000B-1...
  • Page 8 All manuals and user guides at all-guides.com HYGROSTATS H46C,E H46C SCHÉMA INTERNE DE Q539A T87F Fig. 6. Schéma de câblage en série type du H46C et du T87F/Q539A pour assurer la déshumidification et empêcher le développement de moisissure. REGLAGE VERIFICATION Les contacts du H46 se ferment sur une hausse Une fois le montage et le raccordement terminés, mettre...

Ce manuel est également adapté pour:

H46e