Installing Pump in Sump
These pumps are usually installed in concrete or fiberglass
basins with the lift-out rail system. Figure 3 shows pump
mounted on the rail system. Instructions for installing rail
system are furnished with rail package.
If pump is not installed with lift-out rail system it must be
properly supported on legs and connected to discharge
pipe so that space is provided under pump for entrance
of sewage. Pump inlet should not be closer than 2 inches
from bottom of sump.
It is not generally desirable to install these pumps without
the rail system except on special O.E.M. packaged
systems. Check valves should always be installed along
with shut-off valves. This allows for easier service and
prevents backflow into basin.
FIGURE 3
Sewage Pumps
Model: SWH300/SWH500 & SWHD300/SWHD500
Installation and Service
Starting Pump After Installing in Sump
Before lowering pump into basin, connect power lines
and start motor. Impeller should turn counterclockwise
when looking at impeller.
Service and Repair
Important: Pump should be thoroughly cleaned of trash
and deposits before starting disassembly operations
(pages 6-8).
WARNING
Disconnect all power and control wires to motor at
control panel before starting disassembly operation.
Never rely on opening circuit breaker only.
Operating pump builds up heat and pressure; allow time
for pump to cool to room temperature
8
CAUTION